INSTALLATION

be moved on the discharge pipe or the rubber stops can be adjusted as 

necessary. Cut extra float rod length below lower float stop to prevent 

debris from interfering with float operation.

 11.  Install DC charger (see figure 3) by using anchors provided.  If more 

convenient, the charger may be set on a nearby shelf or ledge.  The 

charger should be located 3 or 4 ft. above the sump.  Then, remove 

protective screen from the front of the charger.

 12.  Connect the leads from the control charger to the battery terminals.  

Positive (+) lead to positive terminal and black neg. (-) lead to negative 

battery terminal.  Upon proper connection, test alarm will momentarily 

sound. This indicates proper charger to battery connection. 

CAUTION

 Correct battery hook up is essential for operation of 

the system.  Use wing nuts supplied with battery and eyelet connectors 

on battery wire leads.  The positive terminal is the larger stud, 3/8" 

diameter.  The smaller stud, 5/16" diameter is the negative terminal.  

Apply grease to the terminals to help prevent corrosion.

 13.  Connect the black lead from the pump to the negative (-) battery 

terminal.  Connect the white lead from the pump to the white lead 

from the switch.  This connection is made at the fuse installed on the 

switch wire (see figure 3).  Connect the black lead from the switch to the 

positive (+) battery terminal.

 14.  Connect the green sensor wire to the sensor connector (figure 3).  

 15.  Close battery box and secure cover.  Carpeted or wood barrier between 

the battery case and the floor is recommended.

 16.  Plug the charger's cord into charger and the 115V wall outlet.  The primary 

sump pump and the control box should be on separate circuits.

 17.  Reconnect power to primary sump pump.
 18.  Optional: A dongle may be used to input a name and number into the 

charger for service information to the end user.

 19.  Optional: On the bottom of the charger there is a pair of dry contacts 

to signal an auxiliary device of a low battery, high water and reverse 

polarity alarm condition. This simple 2-wire connection is rated at a 

maximum of 24V AC/DC and 0.5 amps.  It can be used with an auto-

dialer (such as the Zoeller 10-2616), alarm or home security system.  

Read the auxiliary equipment's documents for further instructions.

  1.  The preferred method of installation for backup pumps is shown in 

Figures 1 and 2.  The installation kit includes the necessary fittings and 

one check valve for installing with the backup  pump discharging into the 

primary pump outlet pipe.  An additional check valve is incorporated in the 

discharge of the backup pump.

    NOTE: Do not install in small spaces where the charger will not be 

properly cooled.

  2.  Remove all parts from shipping carton and make sure all parts are 

included.  Refer to checklist on page 3.

  3.  Select location for battery and control charger.  Control charger must be 

within 6' of a 115V wall outlet and within 6' of pump and basin.  Connect to 

a separate circuit, different than the primary pump.

  4.  If primary pump is installed, disconnect power.
    NOTE: Discharge piping must be 1-1/2" SCH 40 PVC
  5.  Remove the discharge pipe from the pump and put to the side.
  6.  Solvent weld DC pump to tee at a 

30 degree angle

 as shown in Figure 4.

  7.  Install in-line check valve into primary pump discharge.
  8.  Determine the position of the DC pump and measure between the in-

line check valve and tee. Use that measurement to cut discharge pipe.  

Solvent weld that piece first to the tee.  Measure, cut & solvent weld any 

remaining discharge piping above the tee. Finally, connect the discharge 

pipe to the in-line check valve and tighten hose clamp. See Figure 4..

    NOTE:  Check float operations to ensure the hose clamp screws do not 

interfere with the float operation of the primary pump.

  9.  Assemble the float assembly per figure 5.
 10.  Install the float switch assembly bracket above the outlet tee using the 

clamp provided (see figures 1 and 2).  Make certain the clamp is tight on 

the pipe to avoid slippage.  Use electrical tape below the clamp to help 

prevent the clamp from moving.  Ensure that the “off” level of the float is 1" 

min. above the discharge tee of the DC backup pump (see figures 1 and 

2). Position pumps in the sump and move float up and down, making sure 

of free movement without interference from any obstructions inside the 

sump or lid.  Very shallow sumps may require some adjustment to avoid 

overfilling or backing up of water into the sump inlet.  The float switch can 

INITIAL START-UP AND OPERATION

  1.  Test the installation for leaks by running water into the sump allowing 

for normal operation of the primary pump.

  2.  Check the control charger. The “red” power on light will be lit when the 

unit is plugged into the 115V wall outlet. The 

charged/charging

 lights will 

indicate the condition of the battery when the charger has AC power.

  3.  Disconnect primary pump before touching any component in the sump pit.

  4.  Lift float switch. The DC backup pump will run and the alarm will sound. 

Lower float switch immediately after alarm has sounded. Pump is running 

dry during initial check for several seconds. 

CAUTION

 Continuous 

dry running may cause overheating and damage the pump seals. Upon 

release of the float switch, the pump will shut off. Press the reset button 

to turn the alarm off.

  5.  Complete the final testing of your installation by ensuring the primary pump 

is still disconnected from the power. Then, unplug the charger from the 

115V wall outlet.  Run water into the sump until the DC backup pump 

is activated by the float switch. Check all connections for leaks.

  NOTE:  When running the primary pump, it is normal for a stream of 

water to spray out of the 1/8" air relief hole.

  6.  Push alarm reset switch when pump is running. This will silence the alarm. 

The pump will continue to run.

  7.  Reconnect the charger and your primary pump to the AC wall outlets. The 

primary pump should come on and lower the water level in the sump 

back to the normal operating level and shut off.  Use the alarm reset 

button to reset the high water light.  Both primary and backup systems 

are now ready for use.

  8.  The battery charged and charging LED’s will alternate during normal 

charging operation.

    NOTE:  See page 7 for a description of charger functions.

The DC controller is equipped with a 10 amp charger for maintaining the battery in a ready state and recharging the battery after use when AC power 

is restored. Time for recharge depends upon the amount of power consumed by the pumping cycle during the AC power interruption. The pump may 

go back to the ready run position in a very short period of time. A completely drained battery may require up to 24 hours for full recharge. If battery 

does not charge properly, the LCD will display BATFAIL and the alarm will sound.

PERFORMANCE

Discharge: Feet of Head

5

10

15

17.5

Flow: Gal. per Min.

23

15

5

Shut-off Head

The DC pump performance with fully charged 12V battery

Summary of Contents for 507-0005

Page 1: ...state of California to cause cancer and birth defects or other reproductive harm 1 Make sure there is a properly grounded 115V receptacle available Do not use primary pump circuit The location must b...

Page 2: ...chased and used as a backup to a primary dewatering system A complete system includes a Model 507 Basement Sentry and an Aquanot Battery 1 Inspectandtestthesystemforproperoperationsatleastevery3months...

Page 3: ...e DC emergency pump is designed as a backup to your primary sump pump during unexpected power outages or primary pump failure The DC pump electronic controls and all the parts required for installatio...

Page 4: ...DC pump and measure between the in line check valve and tee Use that measurement to cut discharge pipe Solvent weld that piece first to the tee Measure cut solvent weld any remaining discharge piping...

Page 5: ...PRESENT IN MAIN DISCHARGE LINE SEE PUMP INSTALLATION INSTRUCTIONS BATTERY BOX BATTERY BOX OUTLET PRIMARY PUMP IMPORTANT OFF LEVEL OF FLOAT ASSEMBLY MUST BE HIGHER THAN DC BACKUP PUMP 1 MIN SK2499 SK25...

Page 6: ...SUPPLIED BY USER DC BACK UP PUMP CLAMP FLOAT SWITCH WHITE LEAD TO POSITIVE BLACK LEAD TO POSITIVE WHITE LEAD TO DC PUMP BLACK LEAD TO NEGATIVE 15 AMP FUSE DC CHARGER BLACK LEAD TO NEGATIVE TO FLOAT S...

Page 7: ...D will always display the battery voltage and current going to the battery if charging The alarm screen shows current alarms The cycle counter screen shows how many times the DC float has been activat...

Page 8: ...the CO detector to activate Contact the manufacturer and ask for recommendations as to what can be done to prevent the alarm activation MAIL TO P O BOX 16347 Louisville KY 40256 0347 SHIP TO 3649 Can...

Reviews: