 2.3 I  Operati ng

• 

Check that there are no tools or other foreign objects in the machine.

• 

The panel that provides access to the technical secti on must be put in place.

• 

Set the valves as follows: valve B wide open, valves A, C, D and E closed

: water entry valve
: by-pass valve
: water exit valve
: water entry adjustment valve (opti onal)
: water exit adjustment valve (opti onal)

•  An incorrect by-pass setti  ng may cause the heat pump to malfuncti on.

• 

Check that the hydraulic correcti ons are correctly ti ghtened and that there are no leaks.

• 

Check that the device is fully stable.

• 

Set the water circulati on running.

• 

Close valve B gradually so that the fi lter pressure is increased by 150g (0.150 bars).

• 

Open valves A, C and D fully then valve E by half (the air which has built up in the heat pump condenser and the 

fi ltrati on circuit will bleed out). If valves D and E are not present, open valve A wide and close valve C by half.

•  Connect the power supply to the heat pump.

• 

If  the  heat  pump  is  on  standby 

,  press    for  3  seconds 

 appears for 2 

seconds then 

 (diff erent soft ware No. depending on the devices) for 3 seconds , and the water 

and setpoint temperatures are displayed 

, a 2 miute ti mer will start.

• 

Set the temperature you want ("setpoint" temperature).

Aft er the start-up steps for your heat pump: 

• 

 Shut down the water circulati on temporarily (by stopping the fi ltrati on or closing valve B or C) to check that you 

device stops aft er a few seconds (via the acti vati on of the fl ow rate controller).

• 

Reduce the setpoint temperature to below the water temperature to check that the heat pump stops operati ng. 

• 

Switch off  the heat pump by pressing and holding   for 3 seconds and check that it stops

.

  

 2.4 I  User functi ons

2.4.1  Adjusti ng the temperature set point:

• 

Press 

 to increase the temperature by 0.5 °C, 

• 

Press 

 to reduce the temperature by 0.5 °C.

The heat pump stops automati cally when the pool reaches the required temperature.

2.4.2 Locking/unlocking the keyboard

Press and hold 

 and 

 for 3 seconds:  

 or 

.

Summary of Contents for Z300 M4

Page 1: ...H0548600 B 2016 05 Instructions for installation and use English More documents on www zodiac poolcare com Z300 PM30 EverFirst EN...

Page 2: ...er supply Do not handle the electrical elements with wet hands Clean the terminal board or the power supply socket before connection For any component or sub assembly containing a battery do not recha...

Page 3: ...with the device it is vital that you read this installation and user manual as well as the warnings and warranty booklet delivered with the device Failure to do so may result in material damage or ser...

Page 4: ...front rear connectors Anti vibration studs Attachment holes Bottom view of the appliance base for attachment to the ground and location of the anti vibration studs The device must not be installed In...

Page 5: ...to work on the device water entry valve by pass valve water exit valve water entry adjustment valve optional water exit adjustment valve optional water treatment minimum distance To evacuate the conde...

Page 6: ...circuit breaker D curve for calibre see 5 2 I Technical speci cations with a 30 mA dedicated di erential circuit breaker circuit breaker or switch Additional protection may be required during installa...

Page 7: ...be controlled by remote To do so use the remote control kit available as an option For the connection consult the manual supplied with the kit 1 4 2 Heating priority option This function helps to keep...

Page 8: ...For the connection remove the shunt between terminals 7 8 and connect the switch cable in place potential free contact no polarity 220 240V 50Hz Activate the command by pressing for 5 seconds when the...

Page 9: ...son run automatic circulation for at least 12 hours day the longer this time the longer the heat pump will have enough operating range to heat up Cover the basin with a sheet bubble canopy canvas etc...

Page 10: ...alve A wide and close valve C by half Connect the power supply to the heat pump If the heat pump is on standby press for 3 seconds appears for 2 seconds then di erent software No depending on the devi...

Page 11: ...or the interface 2 languages available French and English reversible models only Select the device s operating mode Water heating only Water heating or cooling automatic according to need The light mu...

Page 12: ...intering micro cover provided on the heat pump 3 2 I Maintenance It is recommended that the device be general serviced at least on a yearly basis to ensure proper operation maintain performance levels...

Page 13: ...converted to gas If your heat pump is not in its defrost cycle this is not normal Switch o and disconnect the heat pump immediately and contact your reseller The device is not working If there is no d...

Page 14: ...Automatic if fewer than 4 faults per hour or press faults per hour Cooling circuit high pressure fault Exchanger clogged with dirt Clean the water exchanger Automatic if fewer than 4 faults per hour o...

Page 15: ...n the link cable between the boards By electricity supply disconnection or automatic if the fault disappears Board power supply fault Check the boards power supply Faulty boards Replace the boards 4 3...

Page 16: ...H0548600 B EN 2016 05 15 4 4 I Wiring diagrams 4 4 1 Z300 M4 M5 M7 PM3041 PM3051 PM3061 EverFirst 8M 11M 13M 4 4 2 Z300 T5 PM3053 EverFirst 11T...

Page 17: ...16 H0548600 B EN 2016 05 4 4 3 Z300 MD5 PM3052 EverFirst 11MD 4 4 4 Z300 MD8 PM3072 EverFirst 15MD EN...

Page 18: ...P Low pressure switch ST5 Compressor back ow sensor C1 Ventilator condenser VA Varistor C2 Compressor condenser BLU Blue C3 Filter WHT White D1 Progressive starter GRY Grey EXP VALVE Electronic regula...

Page 19: ...chnical compartment A Z300 PM30 EverFirst B 50 connector to be glued x2 C Gland D Anti vibration studs x5 E Wintering cap x2 F Wintering cover Heating priority G Remote control H Plant room kit I Cond...

Page 20: ...ge category II Nominal absorbed intensity A 7 9 10 3 4 25 13 10 4 4 16 7 4 Maximum absorbed intensity A 10 13 4 7 15 7 12 8 5 24 9 3 Minimum cable section mm 3x2 5 3x2 5 5x2 5 3x4 3x2 5 5x2 5 3x6 5x2...

Page 21: ......

Page 22: ...49180 St Barth l my d Anjou cedex S A S U au capital de 1 267 140 SIREN 395 068 679 RCS PARIS Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Trouvez plus d...

Reviews: