H0548600.B - EN - 2016-05

13

  

 4.2 I  Error code display

Display

Possible causes

Soluti ons

Resetti  ng

Exchanger protecti on in cool 

mode

ST4 sensor temperature 

too low

Wait unti l the exterior temperature 

rises

Automati c

High temperature error 

on evaporator in "cooling" 

mode

ST3 sensor temperature 

over 60°C or evaporator 

scaled up

Clean the evaporator, if problem  

persists, call an approved technician

Automati c if 

ST3 sensor 

temperature 

below 45°C

Phase order fault (on three 

phase models only)

Cabling not respected on 

the appliance's supply 

terminals,

 Invert phases on power terminals 

(appliance switched off  )

By electricity 

supply 

disconnecti on or 
by pressing 

Electricity provider has 

changed the order of the 

phases

Contact the electricity provided to 

fi nd out if your installati on has been 

modifi ed.

Temporary disconnecti on 

of the power supply to one 

or more phases

Low pressure fault on 

cooling circuit

Pressure fault in the low 

pressure circuit (if problem 

persists aft er resetti  ng)

Call an approved technician

Automati c (if 

fewer than 4 

faults per hour) 

or press 

Cooling circuit high pressure 

fault

Exchanger clogged with dirt

 Clean the water exchanger

Automati c (if 

fewer than 4 

faults per hour) 

or press 

Insuffi  cient water fl ow

 Increase fl ow using by-pass, check 

that the pool fi lter is not clogged

Air and water emulsion 

passed into the device

 Check the pool's hydraulic circuit

Flow controller blocked 

 Check the fl ow controller

Compressor discharge 

temperature fault

Compressor discharge 

temperature too high

Call an approved technician

Press   for 3 

seconds

ST1 sensor fault water 

intake sensor

Sensor is faulty or offl  ine  

(J12-A1 connector)

 Reconnect or change the sensor

Cut power or 

press 

ST4 sensor fault fl uid line 

sensor

Sensor is faulty or offl  ine  

(J8-A1 connector)

 Reconnect or change the sensor

By electricity 

supply 

disconnecti on or 

automati c if the 

fault disappears

ST3 sensor fault Defrost 

sensor

Sensor is faulty or offl  ine  

(terminals  1-2 connector 

J3-A2)

 Reconnect or change the sensor

Cut power or 

press 

ST sensor fault air intake 

sensor

Sensor is faulty or offl  ine  

(terminals  3-4 connector 

J3-A2)

 Reconnect or change the sensor

Cut power or 

press 

Summary of Contents for Z300 M4

Page 1: ...H0548600 B 2016 05 Instructions for installation and use English More documents on www zodiac poolcare com Z300 PM30 EverFirst EN...

Page 2: ...er supply Do not handle the electrical elements with wet hands Clean the terminal board or the power supply socket before connection For any component or sub assembly containing a battery do not recha...

Page 3: ...with the device it is vital that you read this installation and user manual as well as the warnings and warranty booklet delivered with the device Failure to do so may result in material damage or ser...

Page 4: ...front rear connectors Anti vibration studs Attachment holes Bottom view of the appliance base for attachment to the ground and location of the anti vibration studs The device must not be installed In...

Page 5: ...to work on the device water entry valve by pass valve water exit valve water entry adjustment valve optional water exit adjustment valve optional water treatment minimum distance To evacuate the conde...

Page 6: ...circuit breaker D curve for calibre see 5 2 I Technical speci cations with a 30 mA dedicated di erential circuit breaker circuit breaker or switch Additional protection may be required during installa...

Page 7: ...be controlled by remote To do so use the remote control kit available as an option For the connection consult the manual supplied with the kit 1 4 2 Heating priority option This function helps to keep...

Page 8: ...For the connection remove the shunt between terminals 7 8 and connect the switch cable in place potential free contact no polarity 220 240V 50Hz Activate the command by pressing for 5 seconds when the...

Page 9: ...son run automatic circulation for at least 12 hours day the longer this time the longer the heat pump will have enough operating range to heat up Cover the basin with a sheet bubble canopy canvas etc...

Page 10: ...alve A wide and close valve C by half Connect the power supply to the heat pump If the heat pump is on standby press for 3 seconds appears for 2 seconds then di erent software No depending on the devi...

Page 11: ...or the interface 2 languages available French and English reversible models only Select the device s operating mode Water heating only Water heating or cooling automatic according to need The light mu...

Page 12: ...intering micro cover provided on the heat pump 3 2 I Maintenance It is recommended that the device be general serviced at least on a yearly basis to ensure proper operation maintain performance levels...

Page 13: ...converted to gas If your heat pump is not in its defrost cycle this is not normal Switch o and disconnect the heat pump immediately and contact your reseller The device is not working If there is no d...

Page 14: ...Automatic if fewer than 4 faults per hour or press faults per hour Cooling circuit high pressure fault Exchanger clogged with dirt Clean the water exchanger Automatic if fewer than 4 faults per hour o...

Page 15: ...n the link cable between the boards By electricity supply disconnection or automatic if the fault disappears Board power supply fault Check the boards power supply Faulty boards Replace the boards 4 3...

Page 16: ...H0548600 B EN 2016 05 15 4 4 I Wiring diagrams 4 4 1 Z300 M4 M5 M7 PM3041 PM3051 PM3061 EverFirst 8M 11M 13M 4 4 2 Z300 T5 PM3053 EverFirst 11T...

Page 17: ...16 H0548600 B EN 2016 05 4 4 3 Z300 MD5 PM3052 EverFirst 11MD 4 4 4 Z300 MD8 PM3072 EverFirst 15MD EN...

Page 18: ...P Low pressure switch ST5 Compressor back ow sensor C1 Ventilator condenser VA Varistor C2 Compressor condenser BLU Blue C3 Filter WHT White D1 Progressive starter GRY Grey EXP VALVE Electronic regula...

Page 19: ...chnical compartment A Z300 PM30 EverFirst B 50 connector to be glued x2 C Gland D Anti vibration studs x5 E Wintering cap x2 F Wintering cover Heating priority G Remote control H Plant room kit I Cond...

Page 20: ...ge category II Nominal absorbed intensity A 7 9 10 3 4 25 13 10 4 4 16 7 4 Maximum absorbed intensity A 10 13 4 7 15 7 12 8 5 24 9 3 Minimum cable section mm 3x2 5 3x2 5 5x2 5 3x4 3x2 5 5x2 5 3x6 5x2...

Page 21: ......

Page 22: ...49180 St Barth l my d Anjou cedex S A S U au capital de 1 267 140 SIREN 395 068 679 RCS PARIS Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Trouvez plus d...

Reviews: