background image

18

❺ Troubleshooting

• 

Before you contact your reseller, please carry out these few simple checks using the following 

tables if a problem occurs. 

• 

If the problem continues contact your reseller.

• 

: Actions reserved for a qualified technician

  

5.1 I  Device behaviour

The device does 

not start heating 

straight away

• 

On start-up, the device remains "paused" for 5 minutes before it starts operating.

• 

When the setpoint temperature is reached, the heat pump stops heating: the water temperature 

is higher than or equal to the setpoint temperature.

• 

When the water flow rate is zero or is not enough, the heat pump stops: check that the water is 

circulating correctly in the heat pump and that the hydraulic connections are correct.

• 

The heat pump stops when the outdoor temperature falls below 5 °C for standard models or 

-5 °C for “Defrost” models.

• 

It may be that the heat pump has detected an operating fault (see § “5.2 I  Error code display”). 

• 

If you have checked these points and the problem persists: contact your reseller.

The device is 

draining water 

• 

Often called condensation, this water is the moisture contained in the air which condenses 

on contact with certain cold mechanisms in the heat pump, especially on the evaporator. The 

more damp the air, the more condensation your heat pump will produce (your device may 

drain several litres of water per day). This water is retrieved by the base of the heat pump and 

drained through a hole. 

• 

To check that the water is not coming from a leak in the pool circuit on the heat pump, shut 

down the heat pump, wait a few minutes and run the filtration pump for the water to circulate 

in the heat pump. If the water continues to flow through the condensation drain, there is a 

water leak in the heat pump; contact your reseller.

The evaporator is 

iced over

• 

Your heat pump will soon switch to its defrost cycle to melt the ice.

• 

If your heat pump cannot manage to deice its evaporator, it will stop itself; this means that the 

outdoor temperature is too low (below 5 °C for standard models, -5 °C for “Defrost” models).

The device is not 

working

• 

 If there is no display, check the supply voltage and the F1 fuse.

• 

When the setpoint temperature is reached, the heat pump stops heating: the water temperature 

is higher than or equal to the setpoint temperature.

• 

When the water flow rate is zero or is not enough, the heat pump stops: check that the water 

is circulating correctly in the heat pump.

• 

The heat pump stops when the outdoor temperature falls below 5 °C for standard models or 

-5 °C for “Defrost” models.

• 

It may be that the heat pump has detected an operating fault (see § “5.2 I  Error code display”). 

The device is 

working but 

the water 

temperature does 

not increase

• 

It may be that the heat pump has detected an operating fault (see § “5.2 I  Error code display”). 

• 

Check that the automatic filling valve is not stuck in open position; this will keep supplying cold 

water into the pool and will prevent the temperature from rising.

• 

There is too much heat loss as the air is cool. Install a heat insulated cover on your pool.

• 

The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean 

it to restore its performances (see § “4.2 I  Maintenance”).

• 

Check that the external environment is not hindering the heat pump (see § “❷ Installation”).

• 

 Check that the heat pump is the right size for this pool and its environment.

The ventilator is 

running but the 

compressor stops 

from time to time 

with no error 

message

• 

If the outdoor temperature is low, the heat pump will perform defrost cycles.

• 

The heat pump is unable to capture enough calories as its evaporator is clogged with dirt. Clean 

it to restore its performances (see § “4.2 I  Maintenance”).

The device trips 

the circuit breaker

• 

 Check that the circuit breaker is correctly dimensioned and that the cable section used 

is 

the right one (see § “1.2 I  Technical specifications”).

• 

 The supply voltage is too low; contact your electricity supplier.

Summary of Contents for Z200

Page 1: ...H0548500_REVF 2021 02 More documents on www zodiac com Z200 Defrost Z200 PI20 Defrost PI20 Instructions for installation and use English Heat pump Translation of the original instructions in French EN...

Page 2: ...sed for any purpose other than that for which it was designed This appliance is not intended for use by individuals including children with impaired physical sensorial or mental abilities or persons l...

Page 3: ...on the appliance with wet hands or if the appliance is wet Before connecting the appliance to the source of supply ensure that the terminal block or supply socket to which the appliance will be conne...

Page 4: ...designated for the recovered refrigerant and labelled for that refrigerant i e special cylinders for the recovery of refrigerant Cylinders shall be complete with pressure relief valve and associated s...

Page 5: ...rinciple 12 3 2 User interface presentation 12 3 3 I Operating 13 3 4 I User functions 14 Maintenance 15 4 1 I Winterizing 15 4 2 I Maintenance 15 Troubleshooting 18 5 1 I Device behaviour 18 5 2 I Er...

Page 6: ...A Z200 PI20 B Joint x2 C Screw in connector x2 D 40 adaptation x2 E 50 reduction x2 F Condensation evacuation kit 15 G Winterizing cap x2 H Winterizing cover Heating priority I Remote control J PAC N...

Page 7: ...cable section mm 3x2 5 3G2 5 Proof pressure bar 6 Service pressure bar 1 5 Max Discharge Suction Pressure bar 42 1 2 Max high pressure low pressure side pressure bar 42 1 2 Head loss mCE 1 1 5 1 1 5...

Page 8: ...on valve and user interface Ventilator Technical access door Pool water intake Pool water output Evaporator Grommet for heating priority cable run Location for drilling for remote control cable run de...

Page 9: ...und The device must not be installed In a closed and unventilated room In a location subject to high winds With the blowing towards a permanent or temporary obstacle window wall hedge awning etc less...

Page 10: ...o make it easier to work on the device water entry valve by pass valve water exit valve water entry adjustment valve optional water exit adjustment valve optional water treatment minimum distance To e...

Page 11: ...hnical specifications with a 30 mA dedicated differential circuit breaker circuit breaker or switch at the head of the line The electricity supply must correspond to the voltage indicated on the devic...

Page 12: ...p power contactor coil filtration timer power contactor tripolar or bipolar for the filtration system pump motor separate cable for the heating priority function heat pump terminal see wiring diagram...

Page 13: ...ing range sufficient to heat Cover the basin with a sheet bubble canopy canvas etc to prevent heat loss Take advantage of a period with mild outdoor temperatures on average 10 C at night your heat pum...

Page 14: ...adually so that the filter pressure is increased by 150g 0 150 bars Open valves A C and D fully then valve E by half the air which has built up in the heat pump condenser and the filtration circuit wi...

Page 15: ...the setpoint temperature is displayed fixed To read the water temperature it is imperative that the filtration is in operation and that the water flow indicator is fixed 3 4 2 Locking unlocking the k...

Page 16: ...nd other personnel working in the surrounding area must be made aware of the work carried out Work conducted in enclosed areas must be avoided Check for the presence of refrigerant The area must be an...

Page 17: ...nd intensity for the equipment being used Typically safe components are the only types on which work can be carried out in the presence of a flammable atmosphere when live The test appliance must fall...

Page 18: ...ll a manifold in order to be able to remove the refrigerant from various locations within the system 6 Make sure that the cylinder is located on the scales before starting recovery operations 7 Start...

Page 19: ...your heat pump cannot manage to deice its evaporator it will stop itself this means that the outdoor temperature is too low below 5 C for standard models 5 C for Defrost models The device is not worki...

Page 20: ...temperature too high 32 C maximum Wait until the temperature falls Flow controller blocked Check the flow controller Water condenser scaled up or blocked Clean the water condenser Outside temperature...

Page 21: ...p relay Earth KM4 Complementary relay C1 Compressor condenser M1 Compressor C2 Ventilator condenser M2 Ventilator CD Flow controller SD1 Water temperature sensor E1 High pressure switch SD2 Air temper...

Page 22: ...KM4 Complementary relay C1 Compressor condenser M1 Compressor C2 Ventilator condenser M2 Ventilator CD Flow controller SD1 Water temperature sensor HP High pressure switch SD2 Air temperature sensor...

Page 23: ...rty of their respective owners Votre revendeur Your retailer Mod le appareil Appliance model Num ro de s rie Serial number Pour plus d informations enregistrement produit et support client For more in...

Reviews: