2. Installation
2.1 Recommendations
Warning: pH Perfect must be installed by an experienced pool professional.
Before carrying out any installation or maintenance of the pH Perfect control centre, disconnect it
from the mains power supplies.
Before starting to install the pH Perfect, check that you have all the components listed above and
ensure you read this instruction manual carefully.
This appliance is not intended for use by persons (including children) that lack experience and
knowledge, unless they have been given supervision or instruction concerning use of the appliance
by a responsible person.
Children should be supervised to ensure that they do not play with the device.
The installation of this device should be carried out by a qualified person in accordance with the
Australian wiring rules AS/NZS 3000.
The control centre should be located in the correct pool zone and connected to supply via a power
outlet that is protected by a residual current device (RCD) having a rated residual operating current
not exceeding 30mA.
The power outlet should have a degree of protection suitable for the pool zone
Ensure that equipotential bonding of all parts of the pool installation is carried out.
During the installation phase of the pH Perfect, check the following:
• that the voltage of the power supply corresponds to the voltage indicated on the side of the
appliance
• that the injection point pressure is lower than 1.5 Bar
• that the peristaltic pump's protection cover is correctly fitted
• that the suction tube is immersed in the corrective solution (pH up or down) container with the
suction tube also connected to the peristaltic pump (left side).
• that the injection tube is connected on one side to the peristaltic pump (right side) and on the
other side to the pool return pipe via the injection valve.
Zodiac Group Australia Pty Ltd will not be held liable for the use of this device with inappropriate
products.
The pH sensor is fragile, it must be handled with care. Try to avoid touching the tip with your fingers.
2.2 Technical details
Dimension (L - W - H)
240 x 200 x 90mm
Weight (appliance, sensor, tube and pipes)
1.7 kg
Power feed 50Hz
220-240 V AC/50 Hz
Consumption 12W
Pump flow rate
1.5 l/hr
Maximum back pressure
1.5 bar
pH control range
0.0 pH-14.0 pH
Appliance accuracy
+/- 0.1 pH
Calibration of the sensor
7.5 pH
If the supply cord is damaged, it shall be replaced by the manufacturer or its
service agent, or similarly qualified person in order to avoid a hazard.