ECI0016PA Data Capture Card User Manual V1.5
Chapter IV Expansion Module
The control card can expand digital IO and analogs AD/DA through CAN bus, ZIO
series CAN bus expansion modules or ZMIO310-CAN series bus expansion modules can
be selected. For details, please refer to corresponding user manuals.
4.1.
Configure as CAN Expansion Module
4.1.1.
ZCAN Slave Protocol Configuration
ECI0016PA is used as IO control card by default. When it is configured as the CAN
bus slave station, ECI0016PA can be used as digital IO expansion module.
When ECI0016pa is used as ZIO expansion module, using CANIO_ADDRESS to
configure CAN address and CAN communication speed. CAN ID addresses correspond to
expanded IO number. For example, when CANIO_ADDRESS=1, IO Number of expanded
ECI0016PA is 32. After CANIO_ADDRESS parameters modified, it is saved into FLASH
automatically, and it will take effect after restart.
Below form shows CAN address and starting IO and AIO Number:
CAN Address
Starting IO No.
Starting AD No.
Starting DA No.
0
16
8
4
1
32
16
8
2
48
24
12
3
64
32
16
4
80
40
20
5
96
48
24
6
112
56
28
7
128
64
32
8
144
72
36
9
160
80
40
10
176
88
44
11
192
96
48
12
208
104
52
13
224
112
56
Summary of Contents for ECI0016PA