ECI0016PA Data Capture Card User Manual V1.5
3.3.
OUT: Digital Output
The digital output adopts one 10Pin screw-type pluggable terminals with a spacing of
3.81mm.
→
Wiring Definition
Terminal
Name
Type
Function 1
OUT0
NPN Leakage type,
low-speed output
Output 0
OUT1
Output 1
OUT2
Output 2
OUT3
Output 3
OUT4
Output 4
OUT5
Output 5
OUT6
Output 6
OUT7
Output 7
IO24V
/
IO power input DC24V
IOGND
/
IO power ground
3.3.1.
Digital Output Specification & Wiring
→
Specification
Item
Low Speed Output (OUT0-7)
Output mode
NPN leakage type, it is 0V when outputs
Frequency
<
8kHz
Voltage level
DC24V
Max output current
+300mA
Max leakage current when off
25μA
Respond time to conduct
12μs
Respond time to close
80μs
Overcurrent protection
Support
Isolation method
optoelectronic isolation
Note:
The times in the form are typical based on the resistive load, and may change