Communication solutions for power utilities
UNIVERSAL POWER-LINE CARRIER SYSTEM TYPE OPU-1
WHOLE BAND QAM MODEM MBPU - Rev. 0 (July 2011)
27/28
S39 General
options
Bit 2...0
Flow control options.
000 Disable flow control (AT&K0).
011 Flow control RTS/CTS (AT&K3).
100 Flow control XON/XOFF (AT&K4).
101 Transparent mode XON/XOFF (AT&K5).
110 Flow control RTS/CTS and XON/XOFF (AT&K6).
Bit 3...7
Reserved.
S41 General
options
Bits 0...2
Reserved.
Bit 3
Modem/modem flow control.
0
Disabled
(AT\G0).
1
Enabled
(AT\G1)
Bit 4
Overspeed.
0
Disabled
(AT%O).
1
Enabled
(AT%O)
Bit 5
Fallback/fallforward (AT%G).
0
Disabled.
1
Enabled.
Bit 6, 7
Reserved.
S91
Point-to-point transmission level
Range:
0 - 15
Units: -dBm
By default:
7
In some cases, for example when the speed is modified, the changes made are not
immediate. Therefore it is advisable to save them in the user profile (AT&W) and carry out
a software or hardware reset to make them effective.