Communication solutions for power utilities
UNIVERSAL POWER-LINE CARRIER SYSTEM TYPE OPU-1
WHOLE BAND QAM MODEM MBPU - Rev. 0 (July 2011)
25/28
Bit 7, 6, 5
Asynchronous format.
0
8N1.
1
7E1
2
7O1
3
8O1
4
7N1
5
8E1.
S25
Delay between the fall of the DTR signal and disconnection
(only bufferized mode). (See AT&D)
Range:
1 - 255
Units:
s (synchronous), 1/100 s (asynchronous)
By default:
5
S26
Delay between the RTS and CTS signals. (See AT&R)
Range:
1 - 255
Units: ms
By default:
10
S27 General
options
Bit 3, 1, 0
Transmission mode (AT&Qn).
000 Direct asynchronous mode. (defect in 0 profile)
001 Selects the on-line synchronous operation mode and
asynchronous in commands.
011
Synchronous
mode.
100 Selects the on-line synchronous operation mode and
asynchronous in commands.
101
Bufferized
asynchronous
mode.
110
Bufferized
asynchronous
mode.
111
Reserved.
Bit 2
Reserved.
Bit 5, 4
Synchronous transmission clock (AT&X).
00
Internal.
01
External.
10
Slave.
Bit 6