Communication solutions for power utilities
UNIVERSAL POWER-LINE CARRIER SYSTEM TYPE OPU-1
WHOLE BAND QAM MODEM MBPU - Rev. 0 (July 2011)
20/28
\G[X]
Modem-modem flow control (XON/XOFF)
\G0
Disable modem-modem flow control. (by default)
\G1
Enable modem-modem flow control.
%G[X] Fallback/Fallforward
%G0 Disabled. (by default)
%G1 Enabled.
&K[X]
Selection of the DTE-modem flow control
&K0
Disable flow control.
&K3
Enable RTS/CTS flow control. (by default)
&K4
Enable XON/XOFF flow control.
&K5
Enable XON/XOFF transparent flow control.
&K6
Enable RTS/CTS and XON/XOFF together.
%L
Received signal level
Sends back the value of the input signal (in negative dBm).
N[X]
Enable automatic modulation detection
N0
Disabled. (by default)
N1
Enabled (equivalent to ATF0).
\N[X]
Asynchronous transmission mode
\N0
Bufferized mode (equal to AT&Q5). (by default)
\N1
Direct mode (equal to AT&Q0).
%O[X] Overspeed
option
The overspeed allows a higher speed tolerance in the V.24 interface in
asynchronous mode.
%O0 Disables overspeed (±1%).
%O1 Enables overspeed (±2.5%). (by default)
&Q Transmission
mode
&Q0
Direct asynchronous mode.
&Q1 Selects synchronous on-line operating mode and asynchronous in
commands. (by default)
&Q2 Selects synchronous on-line operating mode and asynchronous in
commands.