Appendix A: Configuration presets
68
ZP1-X3 Installation Manual
Input and output configuration
Table 28: Inputs and outputs
IN1 Start
MCP Supervised
IN2 Hold
MCP Supervised
IN3 Abort
MCP Supervised
IN4
Manual-only mode activation
Unsupervised
IN5
Low pressure indication
Supervised
IN6
Extinguishing agent flow
Supervised
IN7
Safety door fault monitor
Supervised
IN8 Remote
reset Unsupervised
OUT1 Hold
MCP
Unsupervised
OUT2 Abort
MCP
Unsupervised
OUT3 Manual-only
mode
Unsupervised
OUT4 Extinguishing
released
Unsupervised
OUT5 Fire
sounders Supervised
OUT6 Extinguishing
sounders
Supervised
OUT7
Extinguishing released optical
warning panels or signs
Supervised
OUT8 Actuator
Supervised
Default delays
Table 29: Default delay configuration
Fire sounders delay
0
Fire routing delay [1]
0
Zone delay
0n
Released delay
10 seconds
[1] Requires installation of optional 2010-1-SB expansion board (not supplied).