Chapter 3: Configuration and commissioning
ZP1-X3 Installation Manual
49
Fire panel
Module A
Module B
Module C
Module D
Expansion board configuration
Adding an expansion board
Use this menu, available from the basic or advanced configuration menus, to
configure the number of installed expansion boards. The default value is 00.
To add an expansion board:
1. Set the display as shown below, and then press Enter.
The Expansion I/O Fault/Disabled LED flashes fast to indicate that the
module configuration menu is active.
2. Select a value using the value selection buttons (2 and 4).
Up to four expansion boards can be installed and configured.
3. Press Enter.
4. Save your changes.
Expansion board configuration
Expansion board labels
For configuration purposes expansion boards are labeled A, B, C, and D.
The label for a given module is defined by its position (left to right) in the control
panel cabinet. The first expansion board installed is module A, the second B, etc.
See your expansion board installation sheet for installation instructions.