Zip VP303 Installation, Maintenance And User Instructions Download Page 13

Fault Finding

NB All servicing and repairs must be undertaken by a competent person,
familiar with unvented systems.

Fault

Possible Cause

Solution

Over temperature

The thermostat has failed

Reset. If the cut-out operates

cut-out operates

again isolate the unit and

The thermostat is set at

contact the installer.

too high a temperature

NB Isolate the electrical supply 
before removing the electrical  
cover panel and ensure that the 
panel is correctly replaced and 
secured before reconnecting

Regular, 

Loss of pressure from

Isolate the heating system and 

intermittent water 

the expansion vessel

the mains cold water supply. 

discharge from 

Partly drain the unit. Recharge

tundish

the expansion vessel to the
specified pressure and
re-commission.

Thermostat failure

Isolate the heating system and 
check thermal controls when
discharge ceases. Replace
thermostat if faulty.

Continuous water

Pressure reducing valve

Check with pressure gauge and

discharge from

not operating correctly

replace as necessary

the tundish

P&T relief valve not

Check and replace if faulty

operating correctly

Expansion relief valve not

Check and replace if faulty

operating correctly

No water flow

Cold water mains supply

Restore mains supply to the 

from hot taps

isolated

heater

Integral line strainer in

Check and clean as necessary

pressure reducing valve
has become blocked

Pressure reducing valve

Refit correctly with arrows in

incorrectly fitted

direction of flow

Water from hot

Power supply not

Check and switch on

taps is cold

switched on

Over temperature 

See fault “Over temperature

cut-out has operated

cut-out operates” above

Faulty element

Check and replace as necessary

Thermostat failure

Check and replace as necessary

14

Zip Varipoint III Installation, Maintenance and User Instructions - August 2008  

Varipoint qxd:Varipoint qxd  22/8/08  11:09  Page 12

Summary of Contents for VP303

Page 1: ...mencing installation of the Varipoint unvented water heater Please leave these instructions with the end user after installation Zip Heaters UK Ltd 14 Bertie Ward Way Dereham Norfolk NR19 1TE Telephon...

Page 2: ...a current Registered Operative Identity card for the installation of unvented domestic hot water storage systems issued by an accredited body The Zip Varipoint must be installed in accordance with the...

Page 3: ...External expansion vessel pre charged to 3 5 bar Expansion vessel capacity 5 litre 30 and 50L Varipoint 8 litre 80 and 100L Varipoint Approvals Zip Varipoint III complies with the LVD and EMC directi...

Page 4: ...water supply To drain via tundish Hot water outlet 1 2 9 3 4 5 6 7 8 1 Temperature and pressure relief valve 2 Combined pressure reducing valve and strainer 3 Expansion relief and check valve 4 Balanc...

Page 5: ...the weather These instructions must be read and fully understood before commencing the installation If in doubt or in need of further guidance please ring Zip on 0845 602 4533 Installation must only b...

Page 6: ...perature and pressure relief valves should drain via a tundish which should be installed in a visible location and away from any electrical devices The discharge pipe from the tundish should terminate...

Page 7: ...rge pipe should be at least one pipe size larger than the largest individual discharge pipe to be connected If unvented hot water storage systems are installed where discharges from safety devices may...

Page 8: ...duct Ensure that the wall where the unit is to be located is sufficiently strong to support the full weight of the unit see dimensions and capable of accepting suitable fixings Position the Zip Varipo...

Page 9: ...board or any concealed location For guidance please ring Zip Heaters on 0845 602 4533 Plumbing 1 The unit should be provided with a cold water supply via 22mm pipework 2 The water connections are at t...

Page 10: ...Connect the hot water supply pipe to the outlet from the heater 12 Connect the discharge pipe from the tundish Refer to Installation Requirements on page 6 and Typical Installation drawing on page 5...

Page 11: ...open until all air has been purged from the system and water is flowing freely from all outlets 8 Check for leaks and rectify as necessary 9 Check the operation of both the T P relief valve and the E...

Page 12: ...the electrical supply to the unit isolate the water supply and contact a competent person familiar with unvented systems 9 Please note that lime scale deposits form more readily at higher temperatures...

Page 13: ...n discharge ceases Replace thermostat if faulty Continuous water Pressure reducing valve Check with pressure gauge and discharge from not operating correctly replace as necessary the tundish P T relie...

Page 14: ...and allow the unit to drain De Installation To de install the heater 1 Switch off and disconnect the electrical supply 2 Close the mains water supply isolating valve 3 Drain the heater as described i...

Page 15: ...moval cartage and re installation of any component of the appliance if it needs to be returned for repair to Zip or its Distributor This warranty does not cover damage resulting from non operation of...

Reviews: