Zip AP3/05 Installation, Maintenance And User Instructions Download Page 5

6                                                                

AP3/05, AP3/10, AP3/15 Installation Instructions  

A sacrificial magnesium anode is fitted to the vessel to provide anti-
corrosion protection for the vessel and element. Gradual erosion of the
anode will occur depending upon local conditions and, in extreme cases,
conditions may cause rapid erosion resulting in particles being deposited as 
a residue or emitted from the heater. The Aquapoint should not, therefore, 
be used in critical applications where water quality is paramount. Regular
preventive maintenance inspections are vital to achieve optimum             
performance and durability of the appliance. The condition of the anode 
should be checked regularly by an authorised Zip service provider as part
of the preventive maintenance programme.     

If the hot water system is not used for two weeks or more, it is
recommended that a hot tap be turned on for several minutes at a sink,
basin or bath, but not at a dishwasher, clothes washer or other appliance
before returning to service.

Installation

Requirements

1.  These instructions must be read and fully understood before commencing

the installation. If in doubt, or in need of further guidance, please call Zip
Customer Service on 0845 602 4533.

2.  Zip Aquapoint unvented water heaters must be installed by a competent

installer, familiar with unvented electric water heaters.

3.  Installations must comply fully with UK Water Regulations and any Local 

Authority requirements.

4. The electrical installation including earthing and cross-bonding should comply 

with the current IEE regulations and any Local Authority requirements.

5. The Zip Aquapoint is designed for connection direct to the incoming mains

water supply and accommodation must be made for the expanded water
that will occur with each heating cycle. Regulations permit expanded hot 
water to be accommodated within the supply pipe work provided that no 
check valve, stop valve with loose jumper or other fitting can prevent
reverse flow. 

( See diagram 1 on page 8)

.

Where the expanded water cannot be accommodated in the pipe work and 
the static water supply pressure is under 4 bar fit accessory pack AQ2 
(expansion vessel and check valve). Where static water pressures are likely 
to exceed 4 bar fit accessory pack AQ2 and AQ3 ( pressure reducing valve
and line strainer ). 

( See diagrams 2 and 3 on page 8)

.

New Aquapoint lll qxd:New Aquapoint lll qxd  5/11/08  15:51  Page 5

Summary of Contents for AP3/05

Page 1: ...The terms Zip and Aquapoint are registered trademarks Zip products described in the brochure are manufuctured under one or more of the following patents AU675601 AU637412 AU635979 GBO422305 GB2065848...

Page 2: ...tion 12 Fault Finding 13 Warranty 14 Installation must only be undertaken by a competent person familiar with unvented electric water heaters The Zip Aquapoint must be installed in accordance with the...

Page 3: ...nt Approvals Zip Aquapoint III complies with LVD and EMC directives and is CE endorsed Zip Aquapoint III has been exam ined tested and found when correctly fitted to comply with the requirements of th...

Page 4: ...602 4533 The Zip Aquapoint is an unvented water heater designed for connection directly to the incoming mains water supply and can serve one or more outlets using conventional taps Care should be take...

Page 5: ...nstallation If in doubt or in need of further guidance please call Zip Customer Service on 0845 602 4533 2 Zip Aquapoint unvented water heaters must be installed by a competent installer familiar with...

Page 6: ...with a maximum resistance to flow equivalent to 9 metres of straight pipe 9 An isolating valve must be fitted to the cold water supply 10 Valves and fittings must be of a type required by Water Supply...

Page 7: ...l shown Diagram 1 Inlet pressure less than 4 bar and expanded hot water can be accommodated in the pipe work Diagram 2 Inlet pressure less than 4 bar but expanded hot water cannot be accommodated in t...

Page 8: ...d water supply pipe work as shown in diagrams 1 to 3 7 Flush all pipe work thoroughly before making the final connections to the valves accessories and cold feed to the heater to ensure that any debri...

Page 9: ...to ensure free water flow through the discharge pipe by turning the knob to the left and holding in the open position 9 Set the temperature control knob to the desired position The E position with a...

Page 10: ...space or any other concealed location If there is any sign of leaks or seepage the heater should be isolated from the water supply and switched off from the electrical supply until a competent person...

Page 11: ...unscrewing the element assembly and removing it If the anode is badly corroded it should be replaced after removing it by grasping with long tongs or other suitable tool through the flange opening wh...

Page 12: ...aulty element Thermostat failure Solution Reset If the cut out operates again isolate the unit and contact the installer NB Isolate the electrical supply before removing the electrical cover panel and...

Page 13: ...and re installation of any component of the appliance if it needs to be returned for repair to Zip or its Distributor This warranty does not cover damage resulting from non operation of the appliance...

Reviews: