12                                                                

AP3/05, AP3/10, AP3/15 Installation Instructions  

Schedule

It is recommended that all key components of the heater should be inspected
on a regular basis, no greater than twelve monthly intervals, for continued safe
and efficient operation. The inspection should be carried out by a competent
person familiar with unvented systems and the components to be inspected
should include the following:

1.  Sacrificial anode. The condition of the anode should be checked regularly

by an authorised Zip service provider as part of the preventive maintenance 

programme and to ensure its effectiveness in protecting the vessel and
element from corrosion.

To check the condition of the anode visually through the flange opening first 
remove the thermostat temperature probe and disconnect the electrical
wires to the element before unscrewing the element assembly and 
removing it. 

If the anode is badly corroded it should be replaced after removing it by 
grasping with long tongs or other suitable tool through the flange opening 
while unscrewing the securing nut on top of the vessel.

2.  Expansion relief valve. Check correct operation.

3.  T&P relief valve, if fitted. Check for correct operation.

4.  Expansion vessel, if fitted. Check pressure – refer to label on vessel for

correct pressure.

5.  Integral line strainer, if pressure reducing valve fitted. Inspect and clean

as necessary.

6.  Check that the discharge pipe-work is free of any obstructions.

7.  Check that all electrical connections are tight.

De-Installation

To de-install the heater

1.  Switch off and disconnect the electrical supply.

2.  Close the mains water supply isolating valve.

3.  Disconnect the inlet and outlet water connections at the top of the heater.

4.  Remove the heater.

5. Drain the unit through the hot water supply connection.

New Aquapoint lll qxd:New Aquapoint lll qxd  5/11/08  15:51  Page 11

Summary of Contents for AP3/05

Page 1: ...The terms Zip and Aquapoint are registered trademarks Zip products described in the brochure are manufuctured under one or more of the following patents AU675601 AU637412 AU635979 GBO422305 GB2065848...

Page 2: ...tion 12 Fault Finding 13 Warranty 14 Installation must only be undertaken by a competent person familiar with unvented electric water heaters The Zip Aquapoint must be installed in accordance with the...

Page 3: ...nt Approvals Zip Aquapoint III complies with LVD and EMC directives and is CE endorsed Zip Aquapoint III has been exam ined tested and found when correctly fitted to comply with the requirements of th...

Page 4: ...602 4533 The Zip Aquapoint is an unvented water heater designed for connection directly to the incoming mains water supply and can serve one or more outlets using conventional taps Care should be take...

Page 5: ...nstallation If in doubt or in need of further guidance please call Zip Customer Service on 0845 602 4533 2 Zip Aquapoint unvented water heaters must be installed by a competent installer familiar with...

Page 6: ...with a maximum resistance to flow equivalent to 9 metres of straight pipe 9 An isolating valve must be fitted to the cold water supply 10 Valves and fittings must be of a type required by Water Supply...

Page 7: ...l shown Diagram 1 Inlet pressure less than 4 bar and expanded hot water can be accommodated in the pipe work Diagram 2 Inlet pressure less than 4 bar but expanded hot water cannot be accommodated in t...

Page 8: ...d water supply pipe work as shown in diagrams 1 to 3 7 Flush all pipe work thoroughly before making the final connections to the valves accessories and cold feed to the heater to ensure that any debri...

Page 9: ...to ensure free water flow through the discharge pipe by turning the knob to the left and holding in the open position 9 Set the temperature control knob to the desired position The E position with a...

Page 10: ...space or any other concealed location If there is any sign of leaks or seepage the heater should be isolated from the water supply and switched off from the electrical supply until a competent person...

Page 11: ...unscrewing the element assembly and removing it If the anode is badly corroded it should be replaced after removing it by grasping with long tongs or other suitable tool through the flange opening wh...

Page 12: ...aulty element Thermostat failure Solution Reset If the cut out operates again isolate the unit and contact the installer NB Isolate the electrical supply before removing the electrical cover panel and...

Page 13: ...and re installation of any component of the appliance if it needs to be returned for repair to Zip or its Distributor This warranty does not cover damage resulting from non operation of the appliance...

Reviews: