63 | UPStealth® 2 User Manual
Troubleshooting
Trouble Analysis
Checking Process:
1)
Check system to make sure everything is working properly:
a.) PIM BYPASS (RED) light should be OFF: Power is going through UPStealth 2 UPS 1000W.
b.) Battery Panel/Module LED should be: Blinking White (monitor), or Blue (Charge) or Green (Discharge).
c.) UPStealth 2 UPS 1000W should not have any RED LIGHTS or warning notifications.
2)
Check all AC (Power) connections from the PIM to the other devices. Confirm nothing is loose.
3)
Check that Battery Interconnect Cables between batteries and UPStealth 2 UPS 1000W are all secure and
attached.
Test:
The UPS TEST switch can be utilized as needed to verify the UPStealth 2 UPS 1000W is working properly.
1)
Place the UPS TEST switch in the OFF position to remove utility input power going to the UPStealth 2 UPS
1000W. This will force the system into backup mode. The UPStealth 2 UPS 1000W will then provide power
to the CABINET LOAD and the UPS TEST OUTPUT on the PIM.
2)
Confirm the UPStealth 2 UPS 1000W is in BACKUP MODE:
a.) UPStealth 2 UPS 1000W has BACKUP MODE ON – Solid Green LED.
b.) The Battery Panel/Module LED – Solid Green LED.
3)
If a RUN TIME test is desired it is best to leave the UPS TEST switch in the ON position and turn off the
utility power off at the breaker going to the PIM. This will force the UPStealth 2 UPS 1000W into backup
mode and keep the batteries from being charged.
Troubleshooting Sequence Chart
UPStealth 2 Troubleshooting Flowchart
Summary of Contents for UPStealth 2
Page 2: ......
Page 71: ...UPStealth 2 User Manual 68 Notes ...
Page 72: ...69 UPStealth 2 User Manual Notes ...
Page 73: ......