background image

 

TR1200  

12320-0752-04

  

Page

 

5 / 8 

www.ziehl.de 

  

Installation 

 

The unit can be installed as follows: 

 

Installation in switchgear cabinet on 35 mm mounting rail according to EN 60715

 

 

With screws M4 for installation on walls or panel. (additional latch not included in delivery)

 

Connection according to connection plan or type plate.

 

 
 

Commissioning 

6.1  Control chart 

 

 
 

 

 
 
 

 

 

  

 

[ ] = Unit 
 
Pressing buttons Up/Down 
simultaneously, sets the

 

values to the smallest one

.

 

 
Code-Reset = Press button Set 

2 s

 

while applying control supply voltage. 
(Pin = 504) 
[ ] = Unit 
 
Error codes: 

-EE

 

= under range 

EEE

 

= over range 

Er1

 

= short circuit sensor 

Er2

 

= interruption sensor 

Er8

 

= internal device error 

Er9

 

= invalide parameter 

Display mode

 

Menu m

ode

 

Parameter mode 

 

Summary of Contents for TR1200

Page 1: ...l illuminated Displays the value of the warmest sensor in the digital display 3 Digital display 3 digits red Display of sensor value Display of error codes e g 8Er98 4 Hindmost decimal point red OFF D...

Page 2: ...L S 2 Sensor 2 3 L S 3 Sensor 3 3 L S 4 Sensor 4 3 L S 5 Sensor 5 3 L S 6 Sensor 6 3 L S 7 Sensor 7 nc S 8 Sensor 8 nc S 9 Sensor 9 nc S10 Sensor 10 nc S11 Sensor 11 nc S12 Sensor 12 nc rel Rel Relay...

Page 3: ...ct condition To keep this condition observe the security instructions with the headline Attention written in the instructions manual Ignoring of the security instructions may lead to death physical in...

Page 4: ...figuration RS485 connection Use RS485 Interface only with shielded wires Large cable lengths may shift the potential ground and the transmission can be disturbed Corrective measures can be galvanic se...

Page 5: ...cluded in delivery Connection according to connection plan or type plate 6 Commissioning 6 1 Control chart Unit Pressing buttons Up Down simultaneously sets the values to the smallest one Code Reset P...

Page 6: ...Sensors 1 12 83 L8 3 conductor connection 8 nc8 No sensor connected 8rel8 Relay function 8bus 8 Menu item for configuring the RS485 interface 8Prt 8 Protocol RS485 interface 84858 RS485 protocol 8Mod...

Page 7: ...chnique Terminals of sensor 1 6 are not compatible to terminals sensor 7 12 Parameter configuration not allowed Code lock active The Code lock can be activated as a protection against manipulation of...

Page 8: ...vice address in menu item 8bus 8 8adr8 to 818 12 RTD half duplex operation mode 1x TR 1200 works like 2x TR 600 The TR 1200 transmits the data from Sensors 1 6 on request with address 1 and from Senso...

Reviews: