Appendix SIPROTEC configuration 
 

9.1  Configuration of the TR1200 for SIEMENS SIPROTEC 4-Devices 

The sensor connections and the configuration of the TR 1200 for evaluation on a Siemens SIPROTEC 4 
protection device are described below. While doing so, the Thermo box operation mode is differentiated. 
 

RS485-Bus Settings  

  RS485-Protocol  

8

bus.

8

 

 

8

prt.

8

 

 

8

485

8

 

 

  Set device address in menu item 

8

bus.

8

 

 

8

adr

8

 to  

8

0

8

 

 

  Set number of stop bits in menu item 

8

bus.

8

 

 

8

stp

8

 to  

8

1

8

 

 

  Baud rate and Parity 

8

bus.

8

 

 

8

bdr

8

 96 

 

8

par

8

 to 

8

EuE

8

 (Default settings 9600 Bd, 8E1) 

 

6 RTD Simplex operation mode 

(1x TR 1200 works like 1x TR 600) = Factory setting  

The TR 1200 transmits the data from Sensors 1...6 cyclically every 3s. 

 

Connect Sensors 1…6

 

  Configure Sensors 1...6 in menu item

 

8

SEN.

8

 depending on the connection 

(configure sensors that are not connected as 

8

nc

8

)

 

 

Configure Sensors 7…12 in menu item

 

8

SEN.

8

 as 

8

nc

8

 

  Set device address in menu item 

8

bus.

8

 

8

adr

8

 to 

8

0

8

 

 

6 RTD half duplex operation mode 

(1x TR 1200 works like 1x TR 600)  

The TR 1200 transmits the data from Sensor 1…6 on request with address 1 

 

Connect Sensors 1…6

 

  Configure Sensors 1...6 in menu item

 

8

SEN.

8

 depending on the connection 

(configure sensors that are not connected as 

8

nc

8

)

 

 

Configure Sensors 7…12 in menu item

 

8

SEN.

8

 as 

8

nc

8

 

  Set device address in menu item 

8

bus.

8

 

 

8

adr

8

 to 

8

1

8

.  

 

12 RTD half duplex operation mode

 (1x TR 1200 works like 2x TR 600)  

The TR 1200 transmits the data from Sensors 1...6 on request with address 1,  
and from Sensors 7...12 on request with address 2 

 

Connect Sensors 1…12

 

  Configure Sensors 1...12 in menu item

 

8

SEN.

8

 depending on the connection 

(configure sensors that are not connected as 

8

nc

8

)

 

  Set device address in menu item 

8

bus.

8

 

 

8

adr

8

 to 

8

1

8

 

 
 

9.2  Configuration of the TR1200 for SIEMENS SIPROTEC 5-Devices  

The sensor connections and the configuration of the TR 1200 for evaluation on a Siemens SIPROTEC 5 
protection device are described below. You can connect up to 4 TR1200. The communication is carried  
out with the 

"Modbus protocol"

 (in SIPROTEC 5 

„SUP Serial“ Protocol“

).  

 

The TR 1200 transmits the data from Sensors 1...12 on request with the SIPROTEC 5 address.  

 

Connect Sensors 1…12

 

  Configure Sensors 1...12 in menu item

 

8

SEN.

8

 depending on the connection 

(configure sensors that are not connected as 

8

nc

8

)

 

  RS485-Bus-Protocol  

8

bus.

8

 

 

8

prt.

8

 

 

8

mod

8

 

(Modbus) 

  Set device address in menu item 

8

bus.

8

 

 

8

adr

8

 as in the SIPROTEC 5 Device (e.g. 1-4)

 

  Set number of stop bits in menu item 

8

bus.

8

 

 

8

stp

8

 to  

8

1

8

 

 

  Baudrate and Parity 

change

 

8

bus.

8

 

 

8

bdr

8

 96 

 

8

par

8

 to 

8

no

8

 (Default 9600 Bd, 8E1) 

Note:

 The baud rate and the data format can alternatively be adapted to the default values of  

the TR1200 also in the SIPROTEC 5 device. The connection and the parameter setting of the  
devices are described in SIPROTEC 5 "Function-Group Type Analog Units" in the manual. 

Summary of Contents for TR1200

Page 1: ...l illuminated Displays the value of the warmest sensor in the digital display 3 Digital display 3 digits red Display of sensor value Display of error codes e g 8Er98 4 Hindmost decimal point red OFF D...

Page 2: ...L S 2 Sensor 2 3 L S 3 Sensor 3 3 L S 4 Sensor 4 3 L S 5 Sensor 5 3 L S 6 Sensor 6 3 L S 7 Sensor 7 nc S 8 Sensor 8 nc S 9 Sensor 9 nc S10 Sensor 10 nc S11 Sensor 11 nc S12 Sensor 12 nc rel Rel Relay...

Page 3: ...ct condition To keep this condition observe the security instructions with the headline Attention written in the instructions manual Ignoring of the security instructions may lead to death physical in...

Page 4: ...figuration RS485 connection Use RS485 Interface only with shielded wires Large cable lengths may shift the potential ground and the transmission can be disturbed Corrective measures can be galvanic se...

Page 5: ...cluded in delivery Connection according to connection plan or type plate 6 Commissioning 6 1 Control chart Unit Pressing buttons Up Down simultaneously sets the values to the smallest one Code Reset P...

Page 6: ...Sensors 1 12 83 L8 3 conductor connection 8 nc8 No sensor connected 8rel8 Relay function 8bus 8 Menu item for configuring the RS485 interface 8Prt 8 Protocol RS485 interface 84858 RS485 protocol 8Mod...

Page 7: ...chnique Terminals of sensor 1 6 are not compatible to terminals sensor 7 12 Parameter configuration not allowed Code lock active The Code lock can be activated as a protection against manipulation of...

Page 8: ...vice address in menu item 8bus 8 8adr8 to 818 12 RTD half duplex operation mode 1x TR 1200 works like 2x TR 600 The TR 1200 transmits the data from Sensors 1 6 on request with address 1 and from Senso...

Reviews: