STW1000V2
12090-0709-00
Page
5 / 6
www.ziehl.de
10
Technical data
Rated supply voltage Us:
DC/AC 24
– 240 V
0/50/60 Hz
Tolerance
DC 20,4 - 297 V
AC 20 - 264 V
Power consumption
< 2 W
< 3 VA
Output relay K1:
1 changer
Switching voltage
max. AC 250 V; DC 300 V
min. voltage / current
12 V 10 mA
conventional thermal current Ith
max. 3 A
Switching power max. AC cos φ = 1
750 VA
Contact life electrical
2 x 10
5
switching cycles at AC 250 V / 3 A
5 x 10
5
switching cycles at AC 250 V / 2 A
1 x 10
6
switching cycles at AC 250 V / 0,8 A
switching capacity utilization category
AC-15 Ie = 2 A Ue = 250 V
rated operational current
rated operational voltage
DC-13 Ie = 2 A Ue = 24 V
DC-13 Ie = 0,8 A Ue = 60 V
DC-13 Ie = 0,4 A Ue = 120 V
DC-13 Ie = 0,2 A Ue = 240 V
Inputs:
power input
DC 0/4…20 mA, 20 Ω
voltage input
DC 0…10 V, 63 Ω
switching point / limit value:
limit I
N
Adjustable
0…100 %
Hysteresis Hsy.
Adjustable
5…30 % from the set limit
setting error
< 10 % from the final value
repetitive error
< 0,2 % from the set limit
temperature influence
< 0,05 %/K
Power on suppression d
on
Adjustable
0,1…10 s
response delay d
off
Adjustable
0,1…10 s
Test conditions:
EN 61010-1
Rated impulse voltage
4000 V
Overvoltage category
III
Pollution degree
2
Rated insulation voltage Ui
300 V
On-period
100 %
EMC-tests:
EN 61326-1 industrial environment
Emission
EN 61326-1; CISPR 11 Class B
Immunity
EN 61326-1 industrial environment
Electrical fast transient/Burst
EN 61000-4-4 ±4 kV
Pulse 5/50 ns, f = 5 kHz, t = 15 ms, T = 300 ms
SURGE immunity
IEC 61000-4-5 ±2 kV
Installation conditions:
Permissible ambient temperature
-20 °C ... +55 °C
Permissible storage temperature
-
40 °C …+70 °C
Installation height
< 2000 m over N.N.
Climatic conditions
5-85% rel. F., no condensation
Permissible wiring temperature
-
5 °C …+70 °C
Vibration resistance EN 60068-2-6
2 … 13,2 Hz
±1 mm
13,2 ... 100 Hz
1 g
2…25 Hz
±1,6 mm
25 ... 150 Hz
5 g