Parameters
Explanation
Adjustment
range
Analogue
output I
Function
Analogue output as a transducer
(measurement converter) (kW-Lx) or as a
control output (Load-Lx) for, e.g., linear
phase angle control
off / kW-L123 /
kW-L1 / kW-L2 /
kW-L3 / Load-
L123 / Load-L1 /
Load-L2 / Load-
L3
Mode
0 or 4 mA or individual
… 20 mA
0…20 mA / 4-20
mA / ind. ZP
Zero point
(transducer (meas.
converter))
Power in kW for zero point,
Power in kW for full-scale
-
: Feed-in (export) (excess)
+
: Draw (import
= purchase)
(Zero point and full-scale may also have
different signs)
-
999,99…999,99
kW
Full-scale
(transducer (meas.
converter))
-
999,99…999,99
kW
Individual zero
point
Individual zero point, this is the smallest
value which is controlled on the analogue
output
0 … 10 mA
Set point
(Load / Control)
With sufficient load regulates the analogue
output to this value
-
999,99…999,99
kW
Max. power
(Load / Control)
Max. power consumption of the controlled
load at 20mA
0,1…500,00 kW
Control
speed
Slow (20%)…fast (90%),
Control response = (difference between the
set point-
actual value) * 20…90%
20…90 %
Control interval
The set point value is readjusted in this
interval; fast (0,5s) … slow (60,0s)
00,5…60,0 s
Control tolerance
Difference set point actual > Control
tolerance = Failure of the load is detected,
e.g. due to a thermostat being switch-off;
load on the analogue output is not taken into
account by K1-3 when additional loads are
switched on
5…50 %
Program &
Code
Program no.
Setting the program
1…8
Default settings
Sets the parameter to factory settings
yes / no
Code lock
Switch code lock on/off, Factory Preset code
504, for details please refer to
“
0…9999
Network
DHCP
Allows automatic assignment of an IP
address from the network
on / off
IP address
Setting a fixed IP address
000.000.000.000-
255.255.255.255
Subnet mask
Configuration of the subnet mask
Gateway
Configuration of the gateway
DNS server
Configuration of the DNS server
MAC address
Display of the MAC address
00:12:E4:XX:XX:XX
Options
Language
Choice of the language
German / English
Date
Change of the date
yyyy-mm-dd
Time
Change of the time
hh:mm:ss
Brightness
The brightness to which the display is
dimmed after the expiry of the dimming time
20…99 %
Dimming time
Starts with the last press of a button; after
expiration of the time the display is dimmed
to the set brightness value
10s…01h00m00s
Num. interval
Time interval in which the measured values
are updated (to smooth the display)
00.1…02.0 s
Simulation
Relay
Simulates relay (On / Off)
Function
Complete functional simulation, analogue output and digital inputs