EFR4001IP
12720-0713-00
Page
34 / 53
www.ziehl.de
8.6.1 Explanation of the symbols
= Apply and save value / setting
= Back, value / parameter will not be saved
= Help text on the value / parameter
8.6.2 Display Examples
Display menu
Display time setting
Display limit value setting
8.7 Code lock / Code reset
Program & Code -> code lock
You can protect all parameters by enabling the code lock. The factory setting is Code 504.
In the event of problems with the code lock (forgot the code) the lock can be switched off and the code reset
to 504 when switching the power on by keeping the key pressed up (approx. 4s) until the message
Code off
is
displayed
→
select “Codesperre”.
8.8 Simulation
Simulation -> relays
Here you can set the output relay ON or OFF, independent of the measured value.
That will actually turn the connected loads / consumers ON or OFF!
In addition, the current state of the digital inputs is displayed.
Simulation -> function
In the simulation function a measurement value can be simulated even without connecting measuring inputs.
All functions of the device operate as if this value is actually being measured. Matching with the simulated
measured value, the value at the analogue output (not when control is active) is also output.
The set value is simulated until the simulation is excited by pressing the
or
➔
button several times. If no
key is pressed for 15 minutes the simulation is also exited.
K1
= Relay ON 11-14
K2
= Relay ON 21-24
K3
= Relay ON 31-34
Y1-
Y4
Actual state of the digital inputs,
0
= open,
1
= closed
Psim [kW]
Simulated measures value
t
= active time
= fixed time 1s
Ph
Phase being simulated
P-Meas
Measured value for evaluation
(simulated value +
switched on load / consumers)
Times
Time state
Aout U + I
Value at the analogue output