Remove the sheath
1
2
1
Cable tie for strain relief
2
Clip
Contacting the shielding on the motor
Connect the shielding on the motor side to the PE junction that is located directly on the motor
housing.
For prefabricated motor lines from ZIEHL-ABEGG SE, the shielding connection is provided with a ring
cable eye for the corresponding thread size.
When using non-prefabricated lines, implement the shielding connection by using a suitable shielding
connection system.
5.1.2
ZAdyn4C MRL Bx
5.1.2.1
Power cable / motor cable / control cables
Contacting of the power cable to the ZAdyn4C MRL Bx
The shield of the power cable must be connected to earth potential at the bolt for the earth connection
on the ZAdyn4C MRL Bx.
1
2
3
1.3
Cable tie for strain relief
2
Bolt for the earth connection
Contacting the shielding of the motor line on the ZAdyn4C MRL Bx
Cable length
The maximum line length is 25 m.
When lines over > 25 m are used, compliance with
DIN EN 12015
(electromagnetic compatibility
–
electrical interference) and
DIN EN 12016
(electromagnetic compatibility
–
noise immunity) is no
longer guaranteed.
On the ZAdyn4C MRL Bx, the shielding of the motor line must be connected with earth potential with
the clip provided (see
fi
g.).