5.10
Digital inputs (X-IN)
5.10.1
Connection with external power supply
X-IN
+24V
+24V
_IN
I01
I02
I03
I04
I05
I06
I07
I08
GND
_IN
GND
8*
7*
6*
5*
4*
3*
2*
1*
1*
9*
8*
7*
6*
5*
4*
3*
2*
9*
10*
+24V
0V
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
1
10*
Connection of digital input with external power supply
1
Modulation
()
terminal designation of connector
*
Wire number of the pre-assembled connecting lead X-I
Information
When using the external power supply the bridges between the ter24V / +24V_IN and
GND / GND_IN the pre-assembled control cable X-I are not required. These must be removed!
5.10.2
Connection with internal power supply
X-IN
+24V
+24V
_IN
I01
I02
I03
I04
I05
I06
I07
I08
GND
_IN
GND
2*
9*
8*
7*
6*
5*
4*
3*
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
1
8*
7*
6*
5*
4*
3*
2*
1*
9*
1*
10*
Connection of digital input with internal power supply
1
Modulation
()
terminal designation of connector
*
Wire number of the pre-assembled connecting lead X-I
Information
When using the internal power supply a bridge must be inserted between the terminals
+24V / +24V_IN and between GND / GND_IN. These bridges are already integrated into the pre-
assembled X-I cable.
The cable GND_IN (wire no.10) is not required. This must be removed from the connection
terminal both on the converter side and the control side and insulated.
CAUTION!
Attention!
The internal 24 V power supply is provided solely for the digital inputs. Switching consumer load with
this voltage is prohibited!
Original operating instructions
ZAdyn4C MRL
Electrical installation
R-TBA14_01-GB 1845
Part.-No. 00163419-GB