The factor is entered in the parameter
Power component / ADJ_UDC
for the two ZArec4Cs.
Power component
|
-
"
ADJ_UDC 1,000
|
-
"
1,000
Adj. = U_DC_dr. / U_DC_IN.
12.3
UPS evacuation
In UPS mode, the ZArec4C cannot feed any energy back into the supply network. The energy created
during generator travel is completely discharged via the brake resistor. This enables travel to continue
at a reduced speed for a limited period in case of mains failure.
•
Single-phase UPS: See connection diagram in "Electrical installation/circuit suggestion, ZArec4C
and ZAdyn4C - UPS evacuation"
•
Three phase UPS or diesel generator: See connection diagram in Chapter 5.19
If all three phases of the line connection voltage at terminal X1 fail, the ZArec4C automatically shuts
down the recovery function. If the recovery function is to be shut down regardless of the line
connection voltage, this can be done using the digital input CL. To do this, the parameter
Default
settings/f_CL
should be set to
LockRec
.
During commissioning, the correct function when switching between normal mode and evacuation
mode must be checked.
For further information on UPS evacuation, refer to the "Emergency evacuation" and "Energy saving/-
power feedback unit in conjunction with automatic emergency operation" chapters in the ZAdyn4C
operating instructions.
13
Operating the ZArec4C with the frequency inverters from other
manufacturers
The ZArec4C power feedback unit can also be operated in combination with frequency inverters from
other manufacturers.
13.1
Requirements for the frequency inverter
•
Mains voltage 400 V / 50 or 60 Hz (on request) +10/-15 %
•
Permitted intermediate circuit voltage: Min. 680 VDC
13.2
ZArec4C control and evaluation
Activation of the digital input and evaluation of the digital outputs can be done both via the frequency
inverter as well as the lift control.
13.2.1
EN enable digital input
The ZArec4C has the EN enable digital input.
Technical data
Voltage range
+22
…
26 VDC
Switching level low/high
<5 VDC / >11 VDC
Current consumption at 24 VDC
typ. 8 mA
Clamping range
max. 1.5 mm
2
Function
•
The ZArec4C automatically switches to standby mode after an adjustable period of time.
•
To activate the return feed function, 24 VDC are switched to the EN digital input via a potential-free
contact.
•
The ZArec4C has an internal 24 VDC voltage supply for this purpose.
•
EN may only be activated after the RDY output is active.
•
EN must be deactivated within 1 s after switching off the RDY output.
Original operating instructions
ZArec4C
Operating the ZArec4C with the frequency inverters from other manufacturers
R-TBA14_03-GB 1817 Index 007
Part.-No. 00163436-GB