ZIEHL-ABEGG MAXvent FV31 Series Assembly Instructions Manual Download Page 25

Type of error

Possible cause

Adjustment

Airways blocked

Check for free air passages (supply/exhaust air vents, 

lters)

see "Impeller blocked or dirty" 

Pressure loss different to 
planned

Check fan selection

Vibrations

Imbalance

Check wings/blades for damage, soiling or ice
see "Impeller blocked or dirty" 

Unusual noises

Ball bearing damaged / 
worn

Replacement of the ball bearing by ZIEHL-ABEGG re-
quired

Impeller / blade scrapes / 
brushes

When indicated, clear foreign bodies/dirt from the fan 
see "Impeller blocked or dirty" 

Operation beyond stall 
point

Check for free air passages (supply/exhaust air vents, 

lters)

Fan turns in wrong direction --> See this fault type

In one-speed motor:
Circuit wrong: D instead of 
Y

Connect to suit voltage according to rating plate

8 Service work

8.1 Repairs / maintenance

Attention!

After removal of the motor and/or impeller, the fan must be balanced again! To do so, 
please contact your manufacturer.

In the case of complete dismantling and reinstallation of the fan, checking must be 
carried out before start-up (see start-up).

Please read the Safety instructions chapter before working on the fan!

Before working on the fan, this must be disconnected from the power supply 
and secured against switching back on!

No maintenance work at running fan!

When operating by means of frequency converter, ensure that the waiting time is 
maintained after safety disconnection - see manufacturer

´

s operating instructions 

regarding capacitor discharge time.

Allow maintenance work to be carried out by trained specialists only.

Any faults detected in the electric system/modules/operating equipment must be 
corrected immediately. If these faults are not corrected, the device/system is 
potentially very dangerous. The device/system must therefore not be operated when it 
is faulty.

Wear safety clothing / shoes and cut-resistant safety gloves when handling.

Please observe the safety regulations and the worker

´

s protection rules by all 

maintenance and service work (EN 50 110, IEC 364).

Assembly instructions 

MAXvent

Service work

L-BAL-F054-GB 2018 Index 005

Part.-No. 00501414-GB

25/32

Summary of Contents for MAXvent FV31 Series

Page 1: ...MAXvent Type FV31 FV14 and DN31 DN14 Medium pressure axial fans Assembly instructions Keep for reference L BAL F054 GB 2018 Index 005 Part No 00501414 GB english...

Page 2: ...10 2 9 Operator s obligation of diligence 11 2 10 Employment of external personnel 11 3 Product overview 11 3 1 Area of application Notes on use 11 3 2 Device construction 12 3 3 Note on the ErP direc...

Page 3: ...Trouble shooting 23 7 1 Code of behaviour in the event of faults 23 7 2 Possible causes and remedial measures 24 8 Service work 25 8 1 Repairs maintenance 25 8 2 Cleaning 27 9 Enclosure 28 9 1 EC Dec...

Page 4: ...n assembly instructions and the motor operating instructions In particular this applies to safety instructions storage transport assembly and service If necessary you can request the motor operating i...

Page 5: ...s or modi cations 1 5 Copyright These assembly instructions contain copyright protected information The assembly instructions may be neither completely nor partially photocopied reproduced translated...

Page 6: ...ve quali cation tests Depending on the installation conditions and the other system components in use e g frequency inverter incl parameter con guration in individual cases there may be unusual noises...

Page 7: ...l abilities Moreover the minimum legal age must be observed the users must be adequately trained 2 2 Intended use Attention The fans are only intended for the conveyance of air or mixtures similar to...

Page 8: ...o t kit Do not climb onto fans without suitable aids Unauthorised constructional modi cations to the fan Operation of the fan as a safety component or for the performance of safety relevant functions...

Page 9: ...onal damage Information A separate fault and performance monitoring system with an alarm signal function is necessary in order to prevent personal injuries and material damages during malfunc tions an...

Page 10: ...n automatic restart The fan motor may switch on and off automatically for functional reasons After power failure or mains disconnection an automatic restart of the fan takes place after voltage return...

Page 11: ...personnel Maintenance and service work are frequently carried out by external employees who often do not recognize the speci c situations and the thus resulting dangers These persons must be comprehen...

Page 12: ...rred to as ErP directive the operational area of certain fans within the EU is bound by certain prerequisites The fan may only be used within the EU when it meets the requirements of the ErP directive...

Page 13: ...the weather and protect it from dirt and weather until nal installation Avoid prolonged storage we recommend a maximum of one year consult the manufacturer before starting if stored for longer Inspec...

Page 14: ...A B C D After unpacking proceed as follows Fasten 4 hooks on the fan The hooks must point outwards Assembly instructions MAXvent Product overview L BAL F054 GB 2018 Index 005 Part No 00501414 GB 14 32...

Page 15: ...isposal must be carried out professionally and in an environmentally friendly way in accordance with the respective national legal stipulations Separate the materials by type and in an environmentally...

Page 16: ...turer or operator of the complete system shall ensure that hazards are prevented by appropriate protective constructions which meet the requirements to EN ISO 13857 The custom designs must suit the pr...

Page 17: ...o the motor suspension as required 4 4 Assembly in a humid atmosphere Information If the device is not in use for longer periods in a humid atmosphere it is recommended to operate the motor fan for at...

Page 18: ...position verti cal with side mounting feet possible upon re quest Installation position hori zontal with ange assem bly Installation position verti cal with ange assembly Observe the following points...

Page 19: ...sation Electrical equipment must be checked regularly Loose connections are to be re tightened and damaged lines or cables must be replaced immediately 5 2 Connection Attention The electrical connecti...

Page 20: ...is used Reducing bearing currents when operating on the inverter When operating on the inverter harmful bearing currents can occur in the motor This depends on many factors which in many cases ZIEHL A...

Page 21: ...protection The thermal motor protection is to be implemented depending on the motor design observing the motor manufacturer s instructions For a motor with no temperature monitor in the winding a moto...

Page 22: ...if available is correctly closed and screwed together 9 Connection data complies with the speci cations on the rating plate 10 Is the overheating protection equipment of the motor properly connected 1...

Page 23: ...s after installation If the limit values of the corresponding fan category are exceeded in start up you must have the motor im peller unit checked by an expert and rebalanced if necessary before conti...

Page 24: ...capacity Select capacity according to the rating plate Temperature too low for bearing grease Insert bearing with cold greasing see Fan does not run Fan turns too slowly Line failure Undervoltage Chec...

Page 25: ...te dismantling and reinstallation of the fan checking must be carried out before start up see start up Please read the Safety instructions chapter before working on the fan Before working on the fan t...

Page 26: ...and the motor switching off prematurely For this reason remove deposits in good time see Chapter Cleaning Maintenance interval in accordance with the degree of contamination of the impeller Check the...

Page 27: ...f available corresponding to the installation position must be checked for free passage In case of improper cleaning work no warranty is assumed regarding corrosion formation paint adhesion for unpain...

Page 28: ...I Articles 1 1 2 1 1 5 1 4 1 1 5 1 in EG Machinery Directive 2006 42 EG The manufacturer is ZIEHL ABEGG SE Heinz Ziehl Strasse D 74653 K nzelsau The following harmonised standards have been used EN 60...

Page 29: ...All industrial property rights remain with the above mentioned manufacturer It is prohibited to commission this incomplete machine until it has been secured that the machine into which it was incorpor...

Page 30: ...otation 18 direction of rotation arrow 21 dismantling 23 E EMC Directive 6 EN 13857 6 EN ISO 12100 6 ErP directive 11 F fan airways 23 friction coefcient 16 G guard grilles 6 I Imbalance 22 impeller 6...

Page 31: ...protective devices 18 S safety distances 15 Screw penetration 16 sound power levels 21 Stainless steel 16 star delta starting switch 20 T Thread size 16 Tightening torques 16 W weight 15 Assembly ins...

Page 32: ...tions If you have any questions concerning the use of our products or plan special uses please contact ZIEHL ABEGG SE Heinz Ziehl Stra e 74653 K nzelsau phone 49 0 7940 16 0 info ziehl abegg de http w...

Reviews: