The chain/rope may not touch the impeller and the possibly mounted frequency
inverter when lifting with the lifting beam, otherwise damage is possible.
•
At a weight greater than 25 kg for men / 10 kg for women, the fan should be lifted out
of the package by two persons (according to REFA). The values may differ from
country to country.
4.3 Connection lead & terminal box
Be aware of the following Points:
•
In demanding environments (wet rooms, outdoor installation), connecting cables must
have water draining pipe elbows.
•
If using a terminal box, install this lower than the motor to ensure that water cannot
penetrate through to the controller housing from the connecting cables.
•
Fasten the motor connection cable with cable tie to the motor suspension or guide it
directly through the housing and fasten to the motor suspension as required.
4.4 Assembly in a humid atmosphere
Information
If the device is not in use for longer periods in a humid atmosphere, it is recommended to
operate the motor/fan for at least two hours every month at 80 - 100 % of maximum
speed to remove any moisture that has penetrated inside.
If available, the stationary heaters must be turned on when the motor is not running.
4.5 Assembly of MAXvent fans type FV, DN
For attachment to
fi
xed motor
fl
ange use screws with property class 8.8 or A2-70
(stainless steel) to EN ISO 4014 and provide with suitable screw locking.
Tightening torques M
A
for fastening the fan and accessories:
Thread size
M6
M8
M10
M12
(Special application
with 5-pitch)
Property class 8.8, friction coefcient
µ
ges =
0.12
9.5 Nm
23 Nm
46 Nm
79 Nm
Stainless steel A2-70, friction coefcient
µ
ges = 0.12
6.4 Nm
15.3 Nm
31 Nm
52 Nm
Screw penetration
≥
1.5 x d
≥
1.5 x d
≥
1.5 x d
≥
1.5 x d
Assembly instructions
MAXvent
Mounting
L-BAL-F054-GB 2018 Index 005
Part.-No. 00501414-GB
17/32