If the cable shield cannot be contacted or not contacted suf
fi
ciently due to special
framework conditions, use a separate high-frequency equipotential bonding conduc-
tor between the motor housing and the protective earth bar of the inverter.
–
Install the separate high-frequency equipotential bonding conductor using braided
fl
at copper strips or high-frequency stranded conductors. Solid copper lines are not
suitable for high-frequency earthing due to the current displacement effect.
•
Use suitable common mode
fi
lters at the inverter output.
•
Limit the voltage increase by using suitable output
fi
lters (du/dt
fi
lters).
•
We recommend the use of all-pole sinusoidal
fi
lters.
•
When using all-pole sinusoidal
fi
lters, screened motor leads, metal terminal boxes
and a second earth connection to the motor can be omitted.
•
General recommendation: Continuous operation of the fan / motor below 15 %
of the nominal speed is not economically and technically reasonable.
5.4 Motor protection
The thermal motor protection is to be implemented depending on the motor design,
observing the motor manufacturer
’
s instructions.
•
For a motor with no temperature monitor in the winding, a motor protection switch is
required.
•
For a motor with
“
TP
”
temperature sensors (PTC thermistor) a PTC thermistor relay is
required, e.g. ZIEHL-ABEGG type U-EK230E with disconnection via a contactor.
On the design with PTC thermistor, observe the max. permitted test voltage of 2.5 V.
•
On a motor with KTY or PT100 temperature sensors, a suitable temperature monitor-
ing unit is required.
•
On a motor with
“
TB
”
thermostatic switches, a suitable motor contactor is required,
e.g. ZIEHL-ABEGG type STDT16/25 or AWE/SK with disconnection via a contactor.
Caution! Thermostatic switches switch on again automatically after cooling. The
constructor of the plant must ensure that the fan does not start up automatically, or
that an automatic start-up does not result in any hazard. ZIEHL-ABEGG motor
contactors prevent an automatic restart after the drive has cooled.
Assembly instructions
MAXvent
Electrical installation
L-BAL-F054-GB 2018 Index 005
Part.-No. 00501414-GB
21/32