12.4
Application examples
12.4.1
Installation with ventilation computer CTE/AH-L and main switch Zenec
ECblue BASIC
100%-function
Abzweigdose
Distributor box
3
1
Zenec
Zenec
CTE/AH(X)-L
2
5
4
6
i_abzwd_ecblue_basic_2nd_zenec_cte.eps
07.11.2019
13
1
7 x 1.5 mm
2
: line voltage and "100 % function"
2
5 x 1.5 mm
2
: control cable
3
Branch socket (not in scope of delivery)
4
Control cable at ECblue
5
Cable for line and relay at ECblue
6
conductor 5 not connected
Danger due to electric current
Make absolutely sure that the mains voltage and the control are a suf
fi
cient distance apart!
Assignment 7 x 1.5 mm
2
Terminals No. Zenec
GNYE = PE
PE
1 = N
6
2 = L1
2
3 + 4 = full speed / automatic speed control
9 + 10
5 + 6 = if in Zenec position "0" no failure report is to take place
7 + 8
Assignment 5 x 1.5 mm
2
Terminals No. CTE/AH(X)-L
1 + 2 = setting signal
A / GND (0 - 10 V / 10 - 0 V)
3 + 4 = fault
D3 / D3
Assembly instructions
ECblue BASIC-MODBUS, ECblue BASIC
Enclosure
L-BAL-F079D-GB 2044 Index 002
Part.-No.