Events and status list
This section lists the event and alarm messages that the UPS might display. The messages are listed in
alphabetical order. This section is listed with each alarm message to help you troubleshoot problems (Table 4-1).
4.2.1
Operational Status and Mode(s)
N.º
UPS STATUS INDICATIONS
LED
FAULT
BYPASS
BATTERY INVERTER
1
Initialized
Extinguish
Extinguish
Extinguish
Extinguish
2
Standby Mode
Extinguish
Extinguish
X
Extinguish
3
No Output
Extinguish
Extinguish
X
Extinguish
4
Bypass Mode
Extinguish
Light
X
Extinguish
5
Utility Mode
Extinguish
Extinguish
X
Light
6
Battery Mode
Extinguish
Extinguish
Light
Extinguish
7
Battery Self-diagnostics
Extinguish
Extinguish
Light
Extinguish
8
Inverter is starting up
Extinguish
X
X
Extinguish
9
ECO Mode
Extinguish
X
X
X
10
EPO Mode
Light
Extinguish
X
Extinguish
11
Maintenance Bypass Mode
Extinguish
Extinguish
Extinguish
Extinguish
12
Fault Mode
Light
X
X
X
4.2.2
Fault Information
FAULT
CODE
UPS ALARM WARNING
BUZZER
LED
1
Rectifier Fault
Beep continuously
Fault LED lit
2
Inverter fault(Including Inverter bridge is
shorted)
Beep continuously
Fault LED lit
3
Inverter Thyristor Short
Beep continuously
Fault LED lit
4
Inverter Thyristor Broken
Beep continuously
Fault LED lit
5
Bypass Thyristor Short
Beep continuously
Fault LED lit
6
Bypass Thyristor Broken
Beep continuously
Fault LED lit
7
Fuse Broken
Beep continuously
Fault LED lit
8
Parallel Relay Fault
Beep continuously
Fault LED lit
9
Fan Fault
Beep continuously
Fault LED lit
10
Reserved or not defined
Beep continuously
Fault LED lit
11
Auxiliary power 1 fault
Beep continuously
Fault LED lit
12
Initialization Fault
Beep continuously
Fault LED lit