24 V00 Installation and operating instructions
The conductor cross-section should be dimensioned to avoid power loss in cables
exceeding 1% of rated output power.
The maximum cable lengths depend on the conductor cross-section as follows:
Conductor
cross-section
Maximum cable length
Zeverlution Pro 33K
10mm²
22 m
16mm²
36 m
25mm²
56 m
The required conductor cross-section depends on the inverter model, ambient
temperature, routing method, cable type, cable losses, applicable installation
requirements (installation location) of the country of installation, etc.