Web Server
~
27
~
Step 2: Select “limit output power based on the energy meter reading” and set
out put power<=0W
Step 3: Select the correct smart meter of the PV sysem
Setp 4: Click the “OK” button in bottom-right of this web page to ensure the
setting parameters take effect.
The PV system will automatically to regulate inverter’s output power to make
sure inverter’s output power won’t exceed the load power, in this case, no PV
power can feed into the grid.
Fig. 6-7: Power flow & limitation based on the energy meter reading
For this method position 2 in Fig. 6-8 should be ticked.
Click the “OK” button in bottom-right of this web page to ensure the setting
parameters take effect.
The system power is calculated as following:
P_load – (P_1 + P_2) = P_meter