FV400
Triple IR Flame Detectors
Relay Mode
Fig. 6: Relay Mode Wiring Diagram
Extra COM terminals are provided for wire monitoring or EOL resistors.
Fault relay is continuously activated when detector is normal.
The fire and fault relays can be used as either normally closed or normally open contacts. The contacts are selected
by fitting links to CON4 and CON5 on the terminal board. The links must be fitted for the output to operate.
Other options can be used at the same time as the Relay output.
See Figs. 10 to 12 for wiring of Ancillary Power, Walk-test Input, Remote Indicator Output, RS485 and Video Out-
put.
+24V
0V
NC
NO
NC
NO
1
1
1
1
ALARM RELAY
Select N/C or N/O on CON4
FAULT RELAY
Select N/C or N/O on CON5
ALARM RELAY
FAULT RELAY
CON4
CON5
LINKS
Contact normally closed
Opens in alarm
Contact normally open
Closes in alarm
Contact normally closed
Opens in fault
Contact normally open
Closes in fault