Zeta Alarm Systems.
ZNDC Installation and Operation Manual
Revision 1.0
Part # MAN-ZNDC-01
Page 9
3.3.2 Connecting Power and Network
Connect 24VDC power and RS-485 network signals from the control panel to TB1. The pin-out of
the connector is:
Pins 1, 2, 9, and 10 and required; the remainder are optional. In addition to the power connections
on TB1, also connect earth ground to J1, the metal pin located in the lower left corner of the board
(see section 3.2).
3.4 Network Installation
Note: ZNDC is hard-coded at network address 10.
3.4.1 Classic 2000 Mk II
To install the ZNDC with a Classic 2000 Mk II FACP, connect a cable between the RS485+ and
RS485- terminals on the ZNDC to the RS485+ and RS485- terminals on the panel (terminals 17
and 18). Power the ZNDC from a 24VDC source, either the network power connections on the
panel, a NAC configured as a power supply on the panel, or an IPB-3 power booster. Once the
ZNDC is connected, power up the panel, then scan the network. The ZNDC should appear at
address 10. If it does not, then check your connections and verify that the ZNDC is configured for
Classic 2000 Mk II operation.
Pin
Function
1
RS-485 + In
2
RS-485 – In
3
RS-485 Shield In
4
RS-485 + Out
5
RS-485 – Out
6
RS-485 Shield Out
7
24VDC Out
8
Ground Out
9
24VDC In
10
Ground In
S3OOO
+
-
+
-
+24V
GND +24V
GND
+24V
-
+
+
-
+24V
GND
GND
NDC
NETWORK WIRING DIAGRAM - S3000
ILLUS. 3.4A
17
18
19
20
21
22
23
24
25
26
2
14
35
6
7
8
9
10
ZRM PORT
TO OTHER
NETWORK
DEVICES