PREMIER QUATRO INSTALLATION MANUAL
Software Versions: PANEL 1.52 & LOOP CARD 2.0
Doc No. GLT.MAN-134
PAGE 5
Issue: 1.33 Author: GW/NJ Date: 14/1/2013
2. PREMIER QUATRO OVERVIEW
2.1 ABOUT THE PREMIER QUATRO FIRE ALARM PANEL
The Premier Quatro fire alarm control panel is a 4-
loop, 20 zone analogue addressable Fire Alarm
Control Panel, with 125 devices per loop.
It can support a 64 panel network control panels and
repeater panels.
Sounders, strobes, relays and isolators can be
combined at the same address as smoke detectors,
heat detectors or combined smoke / heat detectors.
The PSE is a switch mode power supply, with a total
rated output current of 5A, with a max output whilst
charging of 4.1A.
Quatro supports all Zeta addressable devices.
The maximum loop length is 2km.
It has 2 conventional sounder output circuits and a
24V DC auxiliary output, each capable of supplying
450mA (each fitted with 0.5A fuses).
The LCD display is 40 x 4 characters.
It has a set of voltage free fire relay contacts rated at
1A SELV.
It has a set of voltage free fault relay contacts rated at
1A SELV. This relay is normally energised to allow a
fault output in the case of total power failure.
It has the ability to disable any point, zone, sounder or
output.
It has a one man test mode, which resets the zone in
test after a few seconds.
It will operate in ambient temperatures of –5 to 40°C.
It will operate in a relative humidity of up to 95% (non
condensing).
It will withstand vibrations between 5 & 150 Hz.
Premier Quatro should be maintained as described in
the User Manual, Maintenance Guide & Log Book.
FUNCTIONS REQUIRED BY EUROPEAN STANDARD EN 54 PART 2
The Premier Quatro fire alarm control panel provides the following mandatory and optional functions as prescribed by the
European standard EN 54 Part 2.
(a) Mandatory Functions
The mandatory functions and corresponding indications provided by this panel are:
fire alarm
fault warning
disabled
quiescent (when the CIE is powered by a power supply conforming to EN 54-4 and no other functional condition is
indicated)
(b) Optional Functions
The options with requirements provided by this panel are:
output to fire alarm devices (i.e. sounders)
delays to outputs
fault signals from points
disablement of addressable points
test
NB the terms 'device' and 'point' are used interchangeably throughout this manual.