![Zeta Premier Quatro Installation Manual Download Page 47](http://html1.mh-extra.com/html/zeta/premier-quatro/premier-quatro_installation-manual_3540819047.webp)
PREMIER QUATRO INSTALLATION MANUAL
Software Versions: PANEL 1.52 & LOOP CARD 2.0
Doc No. GLT.MAN-134
PAGE 46
Issue: 1.33 Author: GW/NJ Date: 14/1/2013
19. PANEL SPECIFICATIONS
19.1 ENCLOSURE SPECIFICATIONS
DESCRIPTION
VALUE
ENCLOSURE SIZE (L x W x D mm)
485 x 477.5 x 125
TOP CABLE ENTRIES
20
BOTTOM CABLE ENTRIES
6
19.2 ELECTRICAL SPECIFICATIONS
ELECTRICAL DESCRIPTION
VALUE
MAINS VOLTAGE
230 V AC + 10% / - 15%
BATTERY VOLTAGE
2 x 12V SLA (27.6V DC @ 20 C) (7Ah – 17Ah)
POWER SUPPLY
NON-INTEGRAL (SWITCH MODE)
DC OUTPUT: Vmax = 31V ,Vmin = 19V
I max A: 4.1 A
Ripple & Noise: <= 0.6V
CIE DC INPUT VOLTAGE
Vmax = 31.5V, Vmin = 19V
CHARGER VOLTAGE
27.6V
CONVENTIONAL SOUNDER OUTPUT (x2)
I max: 450mA
Quiescent voltage: -5 to -9V DC
Active voltage: 18 to 28V DC
End-of-Line Resistance: 4k7 ohm 0.25W
FAULT RELAY OUTPUT (x1)
Normally Energised (C,NO,NC)
Contact rating: 30V DC @ 1A
LOOP VOLTAGE
Vmax 32 V DC Vmin 26 V DC
MAXIMUM LOOP CURRENT
500 mA
NUMBER OF LOOPS
4
MAXIMUM NUMBER OF ZONES
20
MAXIMUM LOOP CAPACITY
125
MAXIMUM LOOP LENGTH
2 km
MAXIMUM LOOP RESISTANCE
44 ohm
MAXIMUM LOOP CAPACITANCE
500 nF
MAXIMUM BAUD RATE
1024
MAXIMUM NETWORK SIZE
64 nodes
MAXIMUM DISTANCE BETWEEN NODES
1 km
CABLE TYPE
Fire Proof 2 core + screen 1.5 mm
2
ALPHA NUMERIC (LCD) DISPLAY
40 x 4 characters
LED INDICATIONS
Fire Zones 1 – 20
Fault / Disable / Test Zones 1 - 20
KEY ENTRY
12 alphanumeric
6 navigational
3 mandatory
4 menu functions (F1, F2, F3, F4)
ENVIRONMENTAL DATA
Temperature: -5 to 40 C
Relative Humidity: 95% Non-Condensing
ENCLOSURE RATING
IP 30
OTHER PORTS
USB
RS485 via plug in network card
TCP/IP via plug in network card
EN 54-2 Optional Functions with Requirements
7.8, 7.11, 8.3, 9.5, 10
19.2 FUSE SPECIFICATIONS
The Premier Quatro Panel has the following Fuses
19.2.1 Power Supply Controller PCB