13. PANEL SPECIFICATIONS 

13.1 ENCLOSURE SPECIFICATIONS 

DESCRIPTION 

VALUE 

ENCLOSURE SIZE 

485 X 478 X 125mm 

TOP CABLE ENTRIES 

20 X 19mm DIA GROMMETED ENTRIES 

BOTTOM CABLE ENTRIES 

6 X 19mm DIA GROMMETED ENTRIES 

REAR CABLE ENTRIES 

N/A 

13.2 ELECTRICAL SPECIFICATIONS 

ELECTRICAL DESCRIPTION 

VALUE 

MAINS VOLTAGE 

230V AC +/- 10% @ 50/60 Hz 

BATTERY VOLTAGE 

24V DC (2 X 12V SLA BATTERY) 

SYSTEM VOLTAGE 

28V DC NOMINAL (19V to 32 V) 

SYSTEM VOLTAGE RIPPLE 

2V PK-PK MAX 

CHARGER SIZE 

UP TO 17AH in 24 Hours 

ZONE VOLTAGE 

21V DC (NOMINAL): Min 17V DC, Max 31.9V DC (17 - 22.5V) 

ZONE ALARM TRIGGERING CURRENT 

Min 20mA, Max 100mA 

ZONE SHORT CIRCUIT CURRENT 

>100mA 

ZONE OPEN CIRCUIT 

Determined by momentatily reversing the zone voltage 

SOUNDER ALARM OUTPUTS 

4 x 400mA @ 29V DC (Nominal) : Min 18.9V DC, Max 31.9V DC 

AUXILIARY FAULT OUTPUT 

1 x RELAY SELV (1A MAX) 

AUXILIARY FIRE OUTPUT 

1 x RELAY SELV (1A MAX) 

F.A.R.E. OUTPUT 

1 X 100mA @ 29V DC : Min 17.2V DC, Max 30.1V DC 

NUMBER OF ZONES 

8/16/24 

MAXIMUM ZONE CAPACITY 

32 DEVICES PER ZONE 

MAXIMUM ZONE CABLE RESISTANCE 

70 ohms 

AUXILIARY SUPPLY 

250mA @ 29 V DC (NOMINAL) : Min 18.9V DC, Max 31.9V DC 

SOUNDER ACTIVATION DELAY 

0-9 MINUTES -IN 1 MIN INCREMENTS 

ZONE END OF LINE DEVICE 

1N4002 DIODE (STRIPE TO POSITIVE) 

SOUNDER END OF LINE DEVICE 

10 K RESISTOR 

CHARGER VOLTAGE 

27.6V @ 25

o

C (NO BATTERY CONNECTED) 

BATTERY DEEP DISCHARGE PROTECTION 

Batteries less than 20.5V 

MAXIMUM ALLOWED BATTERY INTERNAL RESISTANCE 

0.9 Ω 

TOTAL PSU OUTPUT 

5 Amp 

MAXIMUM CHARGING CURRENT 

920mA 

 

 

PANEL LOAD FOR BATTERY CALCULATIONS 

VALUE 

PANEL CURRENT IN MAINS FAIL 

105mA (85 mA with buzzer silenced) 

PANEL CURRENT IN ALARM 

205mA 

 

 

Summary of Contents for Premier M plus

Page 1: ...PREMIER M PLUS INSTALLATION MANUAL Approved Document No GLT MAN 111 Issue 2 8 Author NJ Date 23 07 2012 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL INSTALLATION MANUAL...

Page 2: ...Its Features include Designed to EN54 Parts 2 4 It is available in 8 16 or 24 zones sizes Automatically uses diode bases for line continuity Four common sounder circuits 400mA Each Serial Repeater Ou...

Page 3: ...ERY POWER 9 5 1 CONNECTING THE MAINS POWER 9 5 2 CONNECTING THE BATTERIES 9 6 FIELD DEVICE TERMINATION 10 6 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 10 6 2 AUXILIARY INPUT AND OUTPUT TER...

Page 4: ...void damage by static The best method is to wear an earth strap but touching any earth point e g building plumbing will help to discharge any static Always handle PCBs by their sides and avoid touchin...

Page 5: ...ply with a supply rating IMAX of 5 0 Amps The PSE has a 920mA limited charger output 2 3 ENVIRONMENTAL It will operate in ambient temperatures of 5 to 40 o C It will operate in a relative humidity of...

Page 6: ...BS5839 installations other cable types may be suitable Depending on the environment the cables may need mechanical protection such as a conduit 3 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the...

Page 7: ...ector will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly with European Fire Alarm Panels For more specific device wiring information please re...

Page 8: ...dition to a larger addressable fire alarm system 3 5 3 Fire Alarm Routing Equipment Output F A R E Monitored 24V nominal output This is a 24V 100mA output that activates in any fire condition and is u...

Page 9: ...el box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosur...

Page 10: ...to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls 5 2 CONNECTING THE BATTERIES Figure 4 Battery...

Page 11: ...to the appropriate connector block on the Termination PCB as shown in Figure 6 below For detailed detection and alarm circuit wiring diagrams please refer to pages 6 and 7 Figure 6 Detector and Sound...

Page 12: ...TTING EXTERNAL SOUNDER DELAY IN MINUTES e g The above example would have a delay of 1 minute 0 No Delay 1 1 Minute 2 2 Minutes 3 3 Minutes 4 4 Minutes 5 5 Minutes 6 6 Minutes 7 7 Minutes 8 8 Minutes 9...

Page 13: ...lit The item that has been disabled will now flash 3 quick flashes then on This means that it has been disabled but is still the focus of the disablement select de select operation If scroll is presse...

Page 14: ...PROGRAMME ZONE IN TEST NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press FUNCTION button twice The General Zone test LED is now on...

Page 15: ...ible with this FACP Note that some makes of detector will require a series resistor or diode to be fitted to work properly There is usually a spare connector on the base to accommodate this check inst...

Page 16: ...fault The recommended setting it to monitor via the motherboard 10 5 SOUNDER FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check that all sounder fuse...

Page 17: ...The required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr IALM panel 0 205mA IALM 4x10 x 0 025 1 0A This typical bell current is 25 mA...

Page 18: ...including test mode 6 FAULT RELAY NO CM NC Activates on fault 7 F A R E FIRE ALARM ROUTING EQUIPMENT 8 SND 1 Connect to sounder circuit 1 sirens bells 9 SND 2 Connect to sounder circuit 2 sirens bell...

Page 19: ...Date 23 07 2012 FS5 Sounder circuit 2 400mA time delay 5 x 20mm glass FS6 AUX Supply 250mA time delay 5 x 20mm glass FS7 Sounder circuit 3 400mA time delay 5 x 20mm glass FS8 Sounder circuit 4 400mA t...

Page 20: ...utput 6 B FUSE Fuse for the second 24V output 7 BATTERY Battery connection 2 x 12V SLA batteries wired in series 8 FACTORY ADJUST Charger adjust pot DO NOT ADJUST 9 THERM Battery charger temperature c...

Page 21: ...IRCUIT Determined by momentatily reversing the zone voltage SOUNDER ALARM OUTPUTS 4 x 400mA 29V DC Nominal Min 18 9V DC Max 31 9V DC AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT...

Page 22: ...a SA1 2EN 12 0359 CPD 0143 EN54 2 1997 A1 2002 A2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings PMP8 PMP16 PMP24 Provided op...

Reviews: