PREMIER M PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-111
PAGE
17
Issue : 2.8 Author: NJ Date: 23/07/2012
12. PCB TERMINATION CONNECTIONS
12.1 CONTROL PANEL CONNECTIONS
12.2 CONTROL PANEL CONNECTIONS
CONNECTION NO
DESCRIPTION
USE
1
ZONE 1 to 8 +&-
Connect to Detection Zones 1 to 8
2
ZONE 9 to 16 +&-
Connect to Detection Zones 9 to 16
3
ZONE 17 to 24 +&-
Connect to Detection Zones 17 to 24
4
Power Supply (Earth, 0V, 28V)
Connection to Power Supply Unit
5
FIRE RELAY NO/CM/NC
Activates on fire (including test mode)
6
FAULT RELAY NO/CM/NC
Activates on fault
7
F.A.R.E. +&-
FIRE ALARM ROUTING EQUIPMENT
8
SND 1 +&-
Connect to sounder circuit 1 (sirens/bells)
9
SND 2 +&-
Connect to sounder circuit 2 (sirens/bells)
10
SND 3 +&-
Connect to sounder circuit 3 (sirens/bells)
11
SND 4 +&-
Connect to sounder circuit 4 (sirens/bells)
12
Power Supply Fault (NC, CM)
Connects to PSU fault output relay
13
SERIAL REP A & B
RS485 SERIAL REPEATER CONNECTION
14
AUX SUPPLY
250mA Supply @ System voltage (29-31 V DC)
15
Display PCB
Ribbon cable to Premier M Plus Display PCB
12.3 CONTROL PANEL FUSES
FUSE NO
DESCRIPTION
RATING
FS3
F.A.R.E. Fuse
100mA time delay 5 x 20mm glass
FS4
Sounder circuit 1
400mA time delay 5 x 20mm glass