Zeta Premier M plus Installation Manual Download Page 15

PREMIER M PLUS INSTALLATION MANUAL 

Approved Document No: GLT.MAN-111 

 

PAGE 

14

 

Issue : 2.8 Author: NJ Date: 23/07/2012 

10. GENERAL FAULT FINDING 

10.1 ZONE FAULTS 

The Zone Faults are non-latching faults. That is, if the fault has been cleared, the panel will automatically reset itself. 

Open circuit faults will be indicated by zone(s) fault LED being lit steady, the internal Fault Buzzer will sound and the General Fault 
LED will be lit. 

Short circuit faults will be indicated by zone(s) fault LED and the short circuit LED Flashing, the internal Fault Buzzer will sound and 
the General Fault LED will be lit. 

Suggested Action 

a) 

Check that the correct end of line device has been fitted (1N4002 Diode) 

b) 

Check that the End Of line is fitted the correct way (with Cathode Stripe to zone +ve) 

c) 

Disconnect the wiring for the zone showing fault, and refit the end of line diode at that zone terminal in the panel. If the 

 

fault condition for that zone clears, this confirms there is a wiring fault. 

d) 

Double-check the wiring and the end of line diode on the zone. Trace the fault with consideration for the type of fault 

 

indicated.(HINT: splitting the cable half way down the zone, and fitting the end of line diode to the new end point helps to 

 

determine which section of cable is giving the fault) 

 

Note: A possible fault is a detector head badly seated in a base that is not making a good connection. 

c) 

A short circuit on a zone could be caused by the end of line diode being fitted backwards. 

d) 

Check that the detectors are compatible with this FACP. Note that some makes of detector will require a series resistor or 

 

diode to be fitted to work properly. There is usually a spare connector on the base to accommodate this (check 

 

instructions that came with the detector). 

e) 

Measure the resistance of the zone cabling (Remove from panel and short out end of line). Ideally this should be less than 

 

50 ohms. Above 70 ohms may cause an open circuit fault. 

10.2 SYSTEM FAULT 

A system fault is an abnormal microprocessor running condition due to various unexpected phenomena. 

This will result in the panel attempting to correct itself. Should this fault occur, the System Fault LED, General Fault LED, General 
Fault relay and fault internal buzzer will be constantly active until the control keyswitch is turned from off position to control enable 
position. This should cause this fault condition to reset. If not, consult your supplier. 

10.3 SUPPLY FAULTS 

A power supply fault is indicative of one or more of the following faults: - 

 1.

 

Loss of Mains power – Remedy 

 a)

 

Check mains fuse (in fused mains filter). Also, check that mains power is present. 

 b)

 

Check 24V Supply fuse on PSU board FS1 & FS2. 

 c)

 

Check 28V supply fuse on Termination Board (FS9) 

 2.

 

Loss of Battery power – Remedy 

 a)

 

Check battery fuse in battery link wire. 

 b)

 

Check that battery connections are secure. 

 3.

 

Low Battery – Remedy 

 a)

 

Check battery voltage – replace if necessary. 

 4.

 

Wrong Charging Voltage. 

The charging voltage should be 27.6 V off load at 25oC. (Note that the PSU will turn off the charger voltage when the batteries are 
disconnected) 

 5.

 

Battery High internal resistance. 

In accordance with EN54-4, the power supply will monitor the batteries internal resistance. It will report a fault if the internal 

Summary of Contents for Premier M plus

Page 1: ...PREMIER M PLUS INSTALLATION MANUAL Approved Document No GLT MAN 111 Issue 2 8 Author NJ Date 23 07 2012 8 24 ZONE CONVENTIONAL FIRE ALARM PANEL INSTALLATION MANUAL...

Page 2: ...Its Features include Designed to EN54 Parts 2 4 It is available in 8 16 or 24 zones sizes Automatically uses diode bases for line continuity Four common sounder circuits 400mA Each Serial Repeater Ou...

Page 3: ...ERY POWER 9 5 1 CONNECTING THE MAINS POWER 9 5 2 CONNECTING THE BATTERIES 9 6 FIELD DEVICE TERMINATION 10 6 1 TERMINATING THE DETECTION AND ALARM SOUNDER CIRCUITS 10 6 2 AUXILIARY INPUT AND OUTPUT TER...

Page 4: ...void damage by static The best method is to wear an earth strap but touching any earth point e g building plumbing will help to discharge any static Always handle PCBs by their sides and avoid touchin...

Page 5: ...ply with a supply rating IMAX of 5 0 Amps The PSE has a 920mA limited charger output 2 3 ENVIRONMENTAL It will operate in ambient temperatures of 5 to 40 o C It will operate in a relative humidity of...

Page 6: ...BS5839 installations other cable types may be suitable Depending on the environment the cables may need mechanical protection such as a conduit 3 2 MAINS WIRING RECOMMENDATIONS The Mains supply to the...

Page 7: ...ector will connect the ve to a 470R load resistor or a polarisation diode to enable the detector to work correctly with European Fire Alarm Panels For more specific device wiring information please re...

Page 8: ...dition to a larger addressable fire alarm system 3 5 3 Fire Alarm Routing Equipment Output F A R E Monitored 24V nominal output This is a 24V 100mA output that activates in any fire condition and is u...

Page 9: ...el box If a grommet is removed fill the hole with a brass cable gland If any knockout is removed but subsequently not used it should be covered up The 230Va c Mains cable must be fed into the enclosur...

Page 10: ...to apply power to the panel before connecting any devices to check for correct operation and to familiarise yourself with the fire alarm panels controls 5 2 CONNECTING THE BATTERIES Figure 4 Battery...

Page 11: ...to the appropriate connector block on the Termination PCB as shown in Figure 6 below For detailed detection and alarm circuit wiring diagrams please refer to pages 6 and 7 Figure 6 Detector and Sound...

Page 12: ...TTING EXTERNAL SOUNDER DELAY IN MINUTES e g The above example would have a delay of 1 minute 0 No Delay 1 1 Minute 2 2 Minutes 3 3 Minutes 4 4 Minutes 5 5 Minutes 6 6 Minutes 7 7 Minutes 8 8 Minutes 9...

Page 13: ...lit The item that has been disabled will now flash 3 quick flashes then on This means that it has been disabled but is still the focus of the disablement select de select operation If scroll is presse...

Page 14: ...PROGRAMME ZONE IN TEST NOTE Only one zone can be programmed in test at any one time 1 Insert and turn control key to enabled position 2 Press FUNCTION button twice The General Zone test LED is now on...

Page 15: ...ible with this FACP Note that some makes of detector will require a series resistor or diode to be fitted to work properly There is usually a spare connector on the base to accommodate this check inst...

Page 16: ...fault The recommended setting it to monitor via the motherboard 10 5 SOUNDER FAULTS Check that the correct END of Line resistor has been fitted 10K brown black orange gold Check that all sounder fuse...

Page 17: ...The required standby is 24 hours It will need to operate in alarm for hour Calculate the battery size required TALM 0 5 Hr IALM panel 0 205mA IALM 4x10 x 0 025 1 0A This typical bell current is 25 mA...

Page 18: ...including test mode 6 FAULT RELAY NO CM NC Activates on fault 7 F A R E FIRE ALARM ROUTING EQUIPMENT 8 SND 1 Connect to sounder circuit 1 sirens bells 9 SND 2 Connect to sounder circuit 2 sirens bell...

Page 19: ...Date 23 07 2012 FS5 Sounder circuit 2 400mA time delay 5 x 20mm glass FS6 AUX Supply 250mA time delay 5 x 20mm glass FS7 Sounder circuit 3 400mA time delay 5 x 20mm glass FS8 Sounder circuit 4 400mA t...

Page 20: ...utput 6 B FUSE Fuse for the second 24V output 7 BATTERY Battery connection 2 x 12V SLA batteries wired in series 8 FACTORY ADJUST Charger adjust pot DO NOT ADJUST 9 THERM Battery charger temperature c...

Page 21: ...IRCUIT Determined by momentatily reversing the zone voltage SOUNDER ALARM OUTPUTS 4 x 400mA 29V DC Nominal Min 18 9V DC Max 31 9V DC AUXILIARY FAULT OUTPUT 1 x RELAY SELV 1A MAX AUXILIARY FIRE OUTPUT...

Page 22: ...a SA1 2EN 12 0359 CPD 0143 EN54 2 1997 A1 2002 A2 2006 EN54 4 1997 A1 2002 A2 2006 Control and indicating equipment for fire detection and fire alarm systems for buildings PMP8 PMP16 PMP24 Provided op...

Reviews: