background image

PREMIER AD USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT.MAN-106 

 

 

PAGE 5

 

Issue: 1.02

     

Authorised: GH         Date: 15/03/2004 

 
3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM 
SYSTEM, INCLUDING THE FACP & ITS INTEGRAL PSE 

 

According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings 
(BS5839: Pt 1: 2002), the owner or person having control of the premises should appoint a responsible person 
to oversee the effective operation of the Fire Alarm System (Clause 47.1). 

 

Below is a summary of the main functions the “Responsible Person” is expected to carry out.  This summary is 
not intended to replace Section seven (User responsibilities) of BS5839: Pt 1: 2002 (available from BSI, or your 
local library). It is meant to give a brief outline of user responsibilities for the safe upkeep of the Fire Alarm 
System.  The number in brackets shows the relevant BS5839: Pt 1: 2002 clauses. 

 

The responsible person must:- 

 

1.  Have sufficient authority to carry out the duties associated with being the responsible person (47.2.a) 
2.  Check the system at least once every 24 hours to ensure there are no faults present (47.2.b) 
3.  Ensure there are arrangements for testing and maintaining the system (47.2.c) 
4.  Ensure the log book is up to date, and available for inspection (47.2.d) 
5.  Instruct all relevant occupants on the basic operation of the system, including start evacuation, silence 

alarms, silence faults and system reset (47.2.e) 

6.  Take appropriate action to limit the rate of false alarms (47.2.f) 
7.  Ensure that all detectors and manual call points remain unobstructed at all times (47.2.g) 
8.  Liase with maintenance personnel to ensure that cleaning, maintenance or building work does not interfere 

with the functioning and reliability of the fire alarm system (47.2.h). 

9.  Ensure any changes to the system are recorded with updated drawings, operating instructions etc (47.2.i) 
10.  Ensure that there are spare parts (especially Call point elements) held on site (47.2.j.1&2) 
11.  In the event of a prealarm, determine the cause & take appropriate action (predetermined fire routine if the 

cause is the start of a fire, arrange maintenance if the cause is a contaminated detector head) (47.3) 

 
With the Premier AD Fire Alarm Panel, we recommend the following tests are carried out: - 

 

Daily Inspection

 

• 

Check that the green Power LED is lit. 

• 

If there are any yellow fault LEDs lit, or the green Power LED is not lit, report the fault(s) to the designated 
site maintenance engineer. 

 

Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests) 

• 

Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate. 

• 

Do not test the same device each week. Test a different zone each week using a different call point or 
detector so that eventually, all the devices will be tested. 

• 

Reset the System by pressing 1,2,3 (Stop sounders, Silence fault tone, Reset). 

• 

Turn key to controls enabled. Press the LED Test button. Check that all LEDs light, and the buzzer sounds 

• 

Check that no call points or fire detectors are obstructed in any way. (eg New furniture or decorations) 

 

Quarterly Test (to be carried out by authorised service personnel only)

 

• 

Check that any servicing or repairs required by all previous logbook entries has been undertaken. 

• 

Visual inspection of the batteries and connections. Check the alarm sounders work on battery only. 

• 

Activate a device from each zone to test the fire alarm. (As per weekly test). 

 

Annual Test (to be carried out by authorised service personnel only)

 

• 

Check every detector, call point, sounder and all auxiliary equipment for correct operation. 

• 

Check Transformer output Voltage (32 VAC), Charger Voltage (28.4V off load, adjusted with VR1) & 
Battery Voltage (25-27V) 

 

Every Five Years (to be carried out by authorised service personnel only)

 

• 

Carry out a complete wiring check in accordance with the testing and inspection requirements of the 
relevant National wiring regulations (in the UK this is the IEE Wiring Regulations). The Batteries should be 
replaced because SLA batteries have a working life of 5 years.

 

Summary of Contents for NPAD

Page 1: ...USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Page 2: ...e fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer What to do if the Fire Alarm Panel shows a Fault Yellow LED Write...

Page 3: ...N 6 5 1 HOW THE PREMIER AD INDICATES AN ALARM 5 2 TO TURN OFF THE ALARM SOUNDERS 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E EVACUATE 5 5 RE...

Page 4: ...y evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point Splits the building into Zones each covering a different area of the building...

Page 5: ...y Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenan...

Page 6: ...set return panel to normal condition To silence a panel after an alarm press Stop Start followed by silence Record the LCD details in the log book then press Reset The previous Next buttons by the LCD...

Page 7: ...menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the test code This is a factory preset code which cannot be changed Here the...

Page 8: ...nders will stop within 2 seconds Sounder bases can take up to 8 seconds to stop If the START STOP button is pressed again during this time the panel will start the sounders again 5 3 A SECOND ALARM SI...

Page 9: ...attery connected to the panel Charger Fault indicates there is a problem with the mains supply or one of its fuses Low Battery indicates that the battery voltage has dropped below 21 volts and that th...

Page 10: ...LED will light along with the zone that contains that sounder 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs the responsible person should Turn keyswitch to Controls enabled and press s...

Page 11: ...e position 2 In the disablement section press the DISABLE button Zone 1 disabled will now flash 3 Press SELECT until the Zone or sounder to be disabled is highlighted 4 Press CONFIRM to disable the se...

Page 12: ...4 97 7 14 1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26...

Page 13: ...1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26 2 68 5 110...

Page 14: ...der Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User need...

Page 15: ...ding work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends tha...

Page 16: ...INTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 106 PAGE 16 Issue 1 02 Authorised GH Date 15 03 2004 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Page 17: ...t No GLT MAN 106 PAGE 17 Issue 1 02 Authorised GH Date 15 03 2004 FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Page 18: ...roved Document No GLT MAN 106 PAGE 18 Issue 1 02 Authorised GH Date 15 03 2004 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Page 19: ...call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compl...

Page 20: ...ions of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name in block letters Position Signature Date For and on behalf...

Page 21: ...een provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be und...

Page 22: ...ertificate Name in block letters Position Signature Date For and on behalf of Address Postcode The extent of liability of the signatory is limited to the system described below Extent of the installat...

Page 23: ...m System installed at Premier AD Address Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the r...

Page 24: ...talled at Address The following work is required before the system can be accepted All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for...

Reviews: