background image

PREMIER AD USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT.MAN-106 

 

 

PAGE 10

 

Issue: 1.02

     

Authorised: GH         Date: 15/03/2004 

 
Earth Fault

 

 
The Earth Fault LED lights when the panel detects an earth fault (short circuit to earth) on the wiring to any part of the  
control panel. The panel will function correctly with a single earth fault, but if a second fault occurs it could damage the 
panel. 

 
 
 
 
 
 
 
 

 

 
 
 
Sounder Fault

 

 
The Premier AD has Fault LEDs for each conventional sounder circuit & its Loop Powered sounders. If the conventional 
sounder LED is Flashing there is an open circuit (Check fuse & end of line). If the conventional sounder LED is steady 
there is a short circuit (Check cabling, device polarity & end of line) If there is a fault on the loop sounders, the line 
sounder fault LED will light along with the zone that contains that sounder. 
 

 

 
 
 
 
 
 
 

 
 
 

 
6.2 WHAT TO DO IF A FAULT CONDITION OCCURS 
 

If a fault occurs, the responsible person should: 

 

• 

Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer.

 

• 

Write down the fault (s) in the Log Book at the back of this Manual.  Take appropriate action to correct the fault 
(Usually by contacting the service engineer) 

 
On the Premier AD panel, the fault indications (except system fault) are non latching. That is, when the fault has been 
cleared, the fault indication will turn off. When all faults have been cleared, the panel will return to its quiescent (normal) 
condition. 
When a fault has been rectified the indicator light for that Fault is automatically turned off.  If all Faults are cleared, the 
General Fault light will go out and the Panel’s Internal Sounder will be silent (if not already muted).  

 
6.3 OTHER LED INDICATIONS 
 

DISABLEMENTS 

      TEST 

MODE 

 
 

 

  ***  FAULT  *** 
 

    Earth Fault

 

  ***  FAULT  *** 

 

    Sounder Fault

 

Summary of Contents for NPAD

Page 1: ...USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Page 2: ...e fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer What to do if the Fire Alarm Panel shows a Fault Yellow LED Write...

Page 3: ...N 6 5 1 HOW THE PREMIER AD INDICATES AN ALARM 5 2 TO TURN OFF THE ALARM SOUNDERS 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E EVACUATE 5 5 RE...

Page 4: ...y evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point Splits the building into Zones each covering a different area of the building...

Page 5: ...y Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenan...

Page 6: ...set return panel to normal condition To silence a panel after an alarm press Stop Start followed by silence Record the LCD details in the log book then press Reset The previous Next buttons by the LCD...

Page 7: ...menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the test code This is a factory preset code which cannot be changed Here the...

Page 8: ...nders will stop within 2 seconds Sounder bases can take up to 8 seconds to stop If the START STOP button is pressed again during this time the panel will start the sounders again 5 3 A SECOND ALARM SI...

Page 9: ...attery connected to the panel Charger Fault indicates there is a problem with the mains supply or one of its fuses Low Battery indicates that the battery voltage has dropped below 21 volts and that th...

Page 10: ...LED will light along with the zone that contains that sounder 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs the responsible person should Turn keyswitch to Controls enabled and press s...

Page 11: ...e position 2 In the disablement section press the DISABLE button Zone 1 disabled will now flash 3 Press SELECT until the Zone or sounder to be disabled is highlighted 4 Press CONFIRM to disable the se...

Page 12: ...4 97 7 14 1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26...

Page 13: ...1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26 2 68 5 110...

Page 14: ...der Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User need...

Page 15: ...ding work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends tha...

Page 16: ...INTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 106 PAGE 16 Issue 1 02 Authorised GH Date 15 03 2004 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Page 17: ...t No GLT MAN 106 PAGE 17 Issue 1 02 Authorised GH Date 15 03 2004 FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Page 18: ...roved Document No GLT MAN 106 PAGE 18 Issue 1 02 Authorised GH Date 15 03 2004 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Page 19: ...call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compl...

Page 20: ...ions of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name in block letters Position Signature Date For and on behalf...

Page 21: ...een provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be und...

Page 22: ...ertificate Name in block letters Position Signature Date For and on behalf of Address Postcode The extent of liability of the signatory is limited to the system described below Extent of the installat...

Page 23: ...m System installed at Premier AD Address Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the r...

Page 24: ...talled at Address The following work is required before the system can be accepted All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for...

Reviews: