background image

PREMIER AD USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Approved Document No: GLT.MAN-106 

 

 

PAGE 21

 

Issue: 1.02

     

Authorised: GH         Date: 15/03/2004 

The System is manual. Type & siting of manual call points takes account of the guidelines
  contained in section 3 of BS 5839-1

The system incorporates automatic fire detectors, and account has been taken of reasonably
foreseeable causes of unwanted alarms, particularly in the selection and siting of detectors

An appropriate analogue system has been specified

An appropriate multi-sensor system has been specified

A time-related system has been specified. Details: 

Fire signals from automatic fire detectors result initially in a staff alarm, which delays a 
general alarm / transmission of signals to an alarm receiving centre (delete as applicable)
for             min.

Measures incorporated to limit false alarms. Account has to be taken of the guidance contained
in section 3 of BS 5839-1: 2002 and, more specifically (tick as appropriate):

Appropriate guidance has been provided to the user to enable limitation of false alarms.

Other measures as follows: 

INSTALLATION & COMMISSIONING RECOMMENDATIONS

It is strongly recommended that installation and commissioning be undertaken in accordance with
the recommendations of section 4 and section 5 of BS 5839-1: 2002 respectively.

In accordance with the recommendations of clause 35.2.6 of BS 5839-1:2002, it is recommended
  that following commissioning a soak period of                            should follow
 (enter a period of at least 1 week)
As the system incorporates no more than 50 automatic fire detectors, no soak test is necessary 
  to satisfy the recommendations of BS 5839-1:2002

SOAK TEST

VERIFICATION

Verification that the system complies with BS 5839-1:2002 should be carried out, on completion, in
accordance with BS 5839-1:2002 Clause 43

Yes

No

To be decided by the purchaser or user

MAINTENANCE

It is strongly recommended that, after completion, the system is maintained in accordance with
section 6 of BS 5839-1:2002

USER RESPONSIBILITIES

The user should appoint a responsible person to supervise all matters pertaining to the fire alarm system
in accordance with the recommendations of section 7 of BS 5839-1:2002

 

Summary of Contents for NPAD

Page 1: ...USER MANUAL MAINTENANCE GUIDE LOG BOOK...

Page 2: ...e fire brigade To reset the panel press the reset button If the panel goes back into alarm silence the sounders and call the engineer What to do if the Fire Alarm Panel shows a Fault Yellow LED Write...

Page 3: ...N 6 5 1 HOW THE PREMIER AD INDICATES AN ALARM 5 2 TO TURN OFF THE ALARM SOUNDERS 5 3 A SECOND ALARM SIGNAL FROM A NEW DETECTION ZONE 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E EVACUATE 5 5 RE...

Page 4: ...y evacuation procedure Alarms can come from Smoke or Heat Detectors or manually by a person operating a Manual Call Point Splits the building into Zones each covering a different area of the building...

Page 5: ...y Call point elements held on site 47 2 j 1 2 11 In the event of a prealarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenan...

Page 6: ...set return panel to normal condition To silence a panel after an alarm press Stop Start followed by silence Record the LCD details in the log book then press Reset The previous Next buttons by the LCD...

Page 7: ...menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the test code This is a factory preset code which cannot be changed Here the...

Page 8: ...nders will stop within 2 seconds Sounder bases can take up to 8 seconds to stop If the START STOP button is pressed again during this time the panel will start the sounders again 5 3 A SECOND ALARM SI...

Page 9: ...attery connected to the panel Charger Fault indicates there is a problem with the mains supply or one of its fuses Low Battery indicates that the battery voltage has dropped below 21 volts and that th...

Page 10: ...LED will light along with the zone that contains that sounder 6 2 WHAT TO DO IF A FAULT CONDITION OCCURS If a fault occurs the responsible person should Turn keyswitch to Controls enabled and press s...

Page 11: ...e position 2 In the disablement section press the DISABLE button Zone 1 disabled will now flash 3 Press SELECT until the Zone or sounder to be disabled is highlighted 4 Press CONFIRM to disable the se...

Page 12: ...4 97 7 14 1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26...

Page 13: ...1 56 4 98 7 15 1 57 4 99 7 16 1 58 4 100 7 17 2 59 4 101 7 18 2 60 4 102 7 19 2 61 4 103 7 20 2 62 4 104 7 21 2 63 4 105 7 22 2 64 4 106 7 23 2 65 5 107 7 24 2 66 5 108 7 25 2 67 5 109 7 26 2 68 5 110...

Page 14: ...der Circuits OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED Auxiliary Output Yes No Fault Output Yes No ADDITIONAL INFORMATION Any additional information the User need...

Page 15: ...ding work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends tha...

Page 16: ...INTENANCE GUIDE LOG BOOK Approved Document No GLT MAN 106 PAGE 16 Issue 1 02 Authorised GH Date 15 03 2004 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Page 17: ...t No GLT MAN 106 PAGE 17 Issue 1 02 Authorised GH Date 15 03 2004 FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Page 18: ...roved Document No GLT MAN 106 PAGE 18 Issue 1 02 Authorised GH Date 15 03 2004 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CA...

Page 19: ...call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked for compl...

Page 20: ...ions of section 2 of BS 5839 1 2002 for the system category described below except for the variations if any stated in this certificate Name in block letters Position Signature Date For and on behalf...

Page 21: ...een provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recommended that installation and commissioning be und...

Page 22: ...ertificate Name in block letters Position Signature Date For and on behalf of Address Postcode The extent of liability of the signatory is limited to the system described below Extent of the installat...

Page 23: ...m System installed at Premier AD Address Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accordance with the r...

Page 24: ...talled at Address The following work is required before the system can be accepted All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for...

Reviews: