SIMPLICITY PLUS INSTALLATION MANUAL
Approved Document No: GLT.MAN-107
PAGE 25
Issue 3.16 Author: NRPJ Date: 21/09/2017
12.3 LABELLING THE LOOP DEVICES
1. To add a label, go to configuration menu 2 as described above. Select option 5 to Edit Device.
Use Next / Previous to select the first device to edit. Press Enter, and a cursor will appear at the
start of the 3rd line. Type in the 20 character label for this device, using the caps lock as
necessary.
Optical
Analog: 25 Normal
█
Zone:01 Ad:016
2. Press enter when the label has been entered. Press Next to edit the next device.
3. To skip many addresses, press 1 (for loop 1), or 2 (for loop 2 on a 2 loop simplicity.) The Panel
will then prompt for the address. Type the address and press enter. The panel will now jump to
this address.
Optical
Analog: 25 Normal
Fl 3 Bedroom 303
Zone:01 Ad:016
NOTE: For many installations, only these configuration steps are required.
Enter Loop Address
Loop: 1
Address: 100
12.4 CONFIGURING ASSOCIATED SOUNDERS
On the Simplicity, all detectors are treated as if they have an associated sounder base during the
initial configuration (indicated by the sounder symbol in the top right hand corner of the edit
device screen) . The panel will send the “activate base sounder” command to all address with
this sounder symbol in the event of an alarm.
Optical
Analog: 25 Normal
Fl 3 Bedroom 303
Zone:01 Ad:016
If a loop contains a large number of detectors, and a small number of associated sounder bases, then the sounders might
take a long time (between 4 & 8 seconds) to start.
If this scenario exists, it is possible to speed up operation as shown below. (Note: if every detector has a sounder base, or
if most of the detectors have a sounder base this “speed up operation” will have little or no effect.
1. Press enter, NEXT, followed by 369 to enter Configuration Menu 2. Select option 5 to edit
device status. Select a detector that does NOT have a sounder base attached.
2. Press the Disablement SELECT button. The sounder symbol turns off to show that this detector
no longer has an associated sounder. (Pressing select again will continue to toggle the sounder
on & off.)
Optical
Analog: 25 Normal
Fl 3 Bedroom 303
Zone:01 Ad:016
3. Repeat for all detectors that do not have an associated sounder base fitted.
If a system had say 40 detectors, but only 20 with an ASSOCIATED sounder base, configuring the sounders as shown above
should half the sounder start time.
12.5 SETTING TIME AND DATE
To set the time & date, enter Configuration Menu 2 and select Configure System (6). The System
Menu is now displayed. Select option 1 to set time & date. Enter the Day, Month, Year, Hour &
Minutes as prompted, and press enter to save, or Cancel at any time to exit.
System Menu
1: Clock 4: Timing
2: Zones 5: Misc
3: Alarms 6: Reset
12.6 SETTING A CUSTOM BANNER
On the Simplicity, the default screen shows Simplicity 64 or Simplicity 126 or Simplicity 252 on
the 1st line of the LCD (depending on panel version), and Fire Alarm Panel on the 2nd line. This
can be changed to any 2 lines of 20 Characters that are required. From Menu 2, select configure
system, followed by MISC. Select option 5, Name.
System Menu
1: Clock 4: Timing
2: Zones 5: Misc
3: Alarms 6: Reset
Then type the first line of text, followed by enter, then the second line of text, followed by enter.
This message will now be the screen message when the panel is running normally, with no faults
or alarms present.
Set Panel Name
ABC ELECTRICAL
SOUTH WEST BRANCH_