2
MULTI INPUT MODULE INSTRUCTION MANUAL
General
The SCM-MIM is a six input module that is designed to be DIN mounted inside of a Smart Connect Multi-loop control
panel. It’s powered and interfaced to the panel via a RJ45 connection. The module has six class B inputs that are
commonly used to monitor and raise alarms from any ancillary equipment such as sprinkler flow switches, aspiration
detectors, secondary fire control panels, beam detectors, and external power supplies etc. The module monitors and
transmits the status (normal, open, short, or alarm) of inputs to the control panel. Each input can be programmed to
either give an alarm or technical alarm signal when active.
Installation
1.
Ensure that the installation area is free from any cables or wires that may get caught, and that there is enough
space on the DIN rail to mount the module. Also ensure that the DIN clip underneath the module is in the open
position.
2.
Place the module onto the DIN rail, hooking the metal earth clip underneath onto the rail first.
3.
Once the earth clip is hooked, push the bottom of the module onto the rail so that the module sits flat.
4.
Push the plastic DIN clip (located at the bottom of the module) upwards to lock and secure the module into
position.
5.
Once the module is secured to the DIN rail, simply connect the supplied CAT5E cable to the module’s RJ45 port.
6.
Connect the other end of CAT5E cable to the nearest unoccupied RJ45 port on the termination PCB.
ATTENTION:
THE PANEL MUST BE POWERED DOWN AND DISCONNECTED FROM THE BATTERIES BEFORE
INSTALLING OR REMOVING ANY MODULES.