MULTI INPUT MODULE INSTRUCTION MANUAL 

Wiring recommendations 

 

 

 

 

 

Front Unit LED Indications 

 

LED Indication

 

Description

 

LED Indication

 

Description

 

 

On steady when the input is in an alarm 

condition. 

 

Pulses to show communication between 

the module and the motherboard. 

 

Flashing when the input is in a fault 

condition. 

*When a SCM-MIM circuit is disabled, the Fault LED be steady (yellow). 

 

Specifications 

 

Specification 

SCM-MIM 

Design Standard 

EN54-2 

Approval 

LPCB (Pending) 

Wiring Class 

6 x Class B [Power limited & Supervised] 

Circuit Voltage 

24VDC Nominal  (16V – 24.5V with E.O.L fitted) 

Quiescent Current ( E.O.L) 

48mA 

Alarm Current 

73mA 

Input Maximum Line Impedance 

10Ω 

Maximum Ground Fault Impedance 

10KΩ 

End of Line Resistor 

4K7Ω 

Triggering Resistor 

1KΩ 

Operating Temperature 

-5°C (23°F) to 40°C (104°F) 

Max Humidity 

93% Non-Condensing 

Size (mm) (HxWxD) 

103mm x 97mm x 46mm 

Weight 

0.2KG 

Recommended Cable Sizes 

22 AWG to 18 AWG (0.3mm

2

 to 0.8mm

2

 

Wire Gauge (AWG) 

Maximum Wiring Run (Metres) 

22 

910 

20 

1450 

18 

2300 

RECOMMENDED CABLE:  

Cable should be BS approved FPL, 
FPLR, FPLP or equivalent.  