Zeta Alarm Limited Simplicity Plus SP-64/M User Manual, Maintenance Manual & Log Book Download Page 5

 

SIMPLICITY PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Software Versions: PANEL r7255 & LOOP r7152

 

Approved Document No: GLT.MAN-108

 

 

  

PAGE 4

 

Issue 3.09         Author: NRPJ      Date: 25/5/2017

 

3. USER RESPONSIBILITIES & MAINTAINENCE OF THE FIRE ALARM SYSTEM, 

INCLUDING THE FACP & ITS INTEGRAL PSE 

According to the British Standard Code for Fire Detection and Alarm Systems for Commercial Buildings (

BS 5839-1

), the owner or 

person having control of the premises should appoint a responsible person to oversee the effective operation of the Fire Alarm 
System. 

Below is a summary of the main functions the “Responsible Person” is expected to carry out. This summary is not intended to 
replace Section seven (User responsibilities) of BS 5839-1 (available from BSI, or your local library). It is meant to give a brief outline 
of user responsibilities for the safe upkeep of the Fire Alarm System. The number in brackets shows the relevant BS5839: Pt 1 
clauses. 

The responsible person must:- 

1.

 

Have sufficient authority to carry out the duties associated with being the responsible person (47.2.a) 

2.

 

Check the system at least once every 24 hours to ensure there are no faults present (47.2.b) 

3.

 

Ensure there are arrangements for testing and maintaining the system (47.2.c) 

4.

 

Ensure the log book is up to date, and available for inspection (47.2.d) 

5.

 

Instruct all relevant occupants on the basic operation of the system, including start evacuation, silence alarms, silence 
faults and system reset (47.2.e) 

6.

 

Take appropriate action to limit the rate of false alarms (47.2.f) 

7.

 

Ensure that all detectors and manual call points remain unobstructed at all times (47.2.g) 

8.

 

Liaise with maintenance personnel to ensure that cleaning, maintenance or building work does not interfere with the 
functioning and reliability of the fire alarm system (47.2.h). 

9.

 

Ensure any changes to the system are recorded with updated drawings, operating instructions etc. (47.2.i) 

10.

 

Ensure that there are spare parts (especially Call point elements) held on site (47.2.j.1&2) 

11.

 

In the event of a pre-alarm, determine the cause & take appropriate action (predetermined fire routine if the cause is the 
start of a fire, arrange maintenance if the cause is a contaminated detector head) (47.3)  

With the Simplicity Fire Alarm Panel, we recommend the following tests are carried out: - 

Daily Inspection 

 

Check that the green Power LED is lit. 

 

If there are any yellow fault LEDs lit, or the green Power LED is not lit, report the fault(s) to the designated site 
maintenance engineer. 

Weekly Test (you may wish to temporarily disconnect the Aux relay during the following Tests) 

 

Set off a manual call point or sensor to test the Fire Alarm panel responds and all the sounders activate. 

 

Do not test the same device each week. Test a different zone each week using a different call point or detector so that 
eventually, all the devices will be tested. 

 

Reset the System by pressing 1,2,3 (Stop sounders, Silence fault tone, Reset). 

 

Turn key to CONTROLS ENABLED. Press the LED Test button. Check that all LEDs light, and the buzzer sounds. 

 

Check that no call points or fire detectors are obstructed in any way. (e.g. New furniture or decorations) 

Quarterly Test (to be carried out by authorised service personnel only) 

 

Check that any servicing or repairs required by all previous logbook entries has been undertaken. 

 

Visual inspection of the batteries and connections. Check the alarm sounders work on battery only. 

 

Activate a device from each zone to test the fire alarm. (As per weekly test). 

Annual Test (to be carried out by authorised service personnel only) 

 

Check every detector, call point, sounder and all auxiliary equipment for correct operation. 

 

Check Switch Mode cage INPUT Voltage (30.5 VAC), Charger Voltage (27.6V off load, adjusted with VR1) & Battery Voltage 
(25-27V) 

Every Five Years (to be carried out by authorised service personnel only) 

 

Carry out a complete wiring check in accordance with the testing and inspection requirements of the relevant National 
wiring regulations (in the UK this is the IEE Wiring Regulations). The Batteries should be replaced because SLA batteries 
have a working life of 5 years. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Simplicity Plus SP-64/M

Page 1: ...are Versions PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 Issue 3 09 Author NRPJ Date 25 5 2017 ONE OR TWO LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE L...

Page 2: ...M SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL 7 6 THE FAULT CONDITION 8 6 1 DIFFERENT TYPES OF FAULT 8 6 2...

Page 3: ...LARM PANEL SHOWS A FAULT YELLOW LED Write down the LCD reading and which LEDs are lit either in the log book or on a piece of paper for transferring to the log book later If the supply fault LED is li...

Page 4: ...guished if it can be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operati...

Page 5: ...eld on site 47 2 j 1 2 11 In the event of a pre alarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenance if the cause is a c...

Page 6: ...as possible The Silence Reset Start Stop Sounder buttons are the main control buttons The previous Next buttons by the LCD are used to scroll between fault messages The next button is also used in th...

Page 7: ...ch device or reconfigure the panel Select Covered to exit the menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the test code Th...

Page 8: ...s will stop within 2 seconds Sounder bases can take up to 8 seconds to stop If the START STOP button is pressed again during this time the panel will start the sounders again 5 3 A SECOND ALARM SIGNAL...

Page 9: ...ns failure or a battery failure The LEDs on the Power Supply charger PCB will help the service engineer pinpoint the source of the problem If the mains supply fails the panel will only operate for the...

Page 10: ...s the responsible person should Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer Write down the fault s in the Log Book at the back of this Manual Take...

Page 11: ...E GUIDE LOG BOOK Software Versions PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 10 Issue 3 09 Author NRPJ Date 25 5 2017 6 3 OTHER LED INDICATIONS DISABLEMENTS TEST MODE www acornfires...

Page 12: ...abled Devices 0 4 If more than one zone or sounder needs to be disabled then press DISABLEMENT SELECT again until the required zone or sounder is selected 5 If the panel needs to be taken out of SELEC...

Page 13: ...as contained in each zone QTY SNDR QTY MCP QTY HEADS 1 2 3 4 5 6 7 8 OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED AUXILIARY OUTPUT YES NO FAULT OUTPUT YES NO ADDITIO...

Page 14: ...PE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18...

Page 15: ...PE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18...

Page 16: ...work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fir...

Page 17: ...PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 16 Issue 3 09 Author NRPJ Date 25 5 2017 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL...

Page 18: ...r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 17 Issue 3 09 Author NRPJ Date 25 5 2017 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Page 19: ...T MAN 108 PAGE 18 Issue 3 09 Author NRPJ Date 25 5 2017 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Page 20: ...108 PAGE 19 Issue 3 09 Author NRPJ Date 25 5 2017 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINT...

Page 21: ...oved Document No GLT MAN 108 PAGE 20 Issue 3 09 Author NRPJ Date 25 5 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE...

Page 22: ...Document No GLT MAN 108 PAGE 21 Issue 3 09 Author NRPJ Date 25 5 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING C...

Page 23: ...27V All call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked fo...

Page 24: ...t the said design for which I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 for the system category described below ex...

Page 25: ...s applicable for min Appropriate guidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recomme...

Page 26: ...ith the specifications described below and with the recommendations of BS5839 1 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of...

Page 27: ...endations of BS 5839 1 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accord...

Page 28: ...y this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre oper...

Page 29: ...7 2012 Updated images Fixed Formatting 3 06 26 7 2012 Fixes Table Errors Corrected references to Quatro Panel to Simplicity Panel Moved Modification History back to first page Realigned Page Breaks U...

Reviews: