SIMPLICITY PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK 

Software Versions: PANEL r7255 & LOOP r7152

 

Approved Document No: GLT.MAN-108

 

 

  

PAGE 2

 

Issue 3.09         Author: NRPJ      Date: 25/5/2017

 

WHAT TO DO IF THE FIRE ALARM PANEL SHOWS AN ALARM (RED LED) 

Write down the LCD reading and which LEDs are lit (either in the log book, or on a piece of paper for transferring to the log book 
later). 

Follow the building procedures for fire alarm activation. 

When the building has been evacuated, the sounders can be silenced by turning the key to the on position and pressing the 
Start/Stop Sounder button, then pressing the Silence Tone button (Note that the sounders may take up to 8 seconds to stop). 

If there is no sign of fire, investigate the area that reported the fire CAREFULLY. Check for a detector or a call point with its RED LED 
lit. 

If a detector caused the alarm, look for any innocent phenomena that could have activated it (Steam, cooking food, exhaust smoke, 
excessive dust etc. can all activate a smoke detector). If anything is found, try to clear the room by opening a window. 

If a fire is discovered, either tackle it with fire extinguishers if suitably trained, or call the fire brigade. 

To reset the panel press the reset button. 

If the panel goes back into alarm, silence the sounders and call the engineer. 

WHAT TO DO IF THE FIRE ALARM PANEL SHOWS A FAULT (YELLOW LED) 

Write down the LCD reading and which LEDs are lit (either in the log book, or on a piece of paper for transferring to the log book 
later). 

If the supply fault LED is lit, check if there is a power cut to the building. Check that the mains supply to the fire alarm has not been 
turned off. 

If the Pre-alarm LED is on constantly, this could be either a detector that needs servicing, or the start of a fire (or other phenomena 
that can activate the detector). Investigate the indicated location and take appropriate action. 

If the Pre-alarm LED is flashing and the screen indicates “Confirming” an alarm, this means that there may be a fire at the indicated 
location, but the panel is waiting for a short time before deciding whether to indicate an alarm. If the alarm is confirmed (red LEDs) 
follow the procedures for an alarm (see above). 

All other fault indications will need the service engineer’s attention. Call the engineer as soon as possible. Note that when the alarm 
is in a fault condition, the majority of the system may still function correctly. Extra vigilance should be paid in the area with the fault. 
The alarm may not be operational in this area. 

The panel’s internal buzzer can be silenced by turning the key to the on position and pressing the Silence Tone button. If the fault 
comes and goes, the panel will buzz every time the fault happens. If this is not acceptable you may be able to disable the zone that 
has the fault. 

www.acornfiresecurity.com

www.acornfiresecurity.com

Summary of Contents for Simplicity Plus SP-64/M

Page 1: ...are Versions PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 Issue 3 09 Author NRPJ Date 25 5 2017 ONE OR TWO LOOP ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL USER MANUAL MAINTENANCE GUIDE L...

Page 2: ...M SIGNAL FROM A NEW DETECTION ZONE 7 5 4 TURNING ON THE ALARM SOUNDERS FROM THE FACP I E TO EVACUATE THE BUILDING 7 5 5 RESETTING THE PANEL 7 6 THE FAULT CONDITION 8 6 1 DIFFERENT TYPES OF FAULT 8 6 2...

Page 3: ...LARM PANEL SHOWS A FAULT YELLOW LED Write down the LCD reading and which LEDs are lit either in the log book or on a piece of paper for transferring to the log book later If the supply fault LED is li...

Page 4: ...guished if it can be safely tackled or the local fire brigade called according to the company evacuation procedure 2 An Alarm can be raised from Smoke or Heat Detectors or manually by a person operati...

Page 5: ...eld on site 47 2 j 1 2 11 In the event of a pre alarm determine the cause take appropriate action predetermined fire routine if the cause is the start of a fire arrange maintenance if the cause is a c...

Page 6: ...as possible The Silence Reset Start Stop Sounder buttons are the main control buttons The previous Next buttons by the LCD are used to scroll between fault messages The next button is also used in th...

Page 7: ...ch device or reconfigure the panel Select Covered to exit the menu iv TEST MODE SELECTION FOR TEST ENGINEER ONLY This access level is obtained by pressing the test button and entering the test code Th...

Page 8: ...s will stop within 2 seconds Sounder bases can take up to 8 seconds to stop If the START STOP button is pressed again during this time the panel will start the sounders again 5 3 A SECOND ALARM SIGNAL...

Page 9: ...ns failure or a battery failure The LEDs on the Power Supply charger PCB will help the service engineer pinpoint the source of the problem If the mains supply fails the panel will only operate for the...

Page 10: ...s the responsible person should Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer Write down the fault s in the Log Book at the back of this Manual Take...

Page 11: ...E GUIDE LOG BOOK Software Versions PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 10 Issue 3 09 Author NRPJ Date 25 5 2017 6 3 OTHER LED INDICATIONS DISABLEMENTS TEST MODE www acornfires...

Page 12: ...abled Devices 0 4 If more than one zone or sounder needs to be disabled then press DISABLEMENT SELECT again until the required zone or sounder is selected 5 If the panel needs to be taken out of SELEC...

Page 13: ...as contained in each zone QTY SNDR QTY MCP QTY HEADS 1 2 3 4 5 6 7 8 OUTPUT ROUTING INFORMATION TYPE OF OUTPUT CONNECTED WHAT HAPPENS WHEN ACTIVATED AUXILIARY OUTPUT YES NO FAULT OUTPUT YES NO ADDITIO...

Page 14: ...PE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18...

Page 15: ...PE LABEL ADDR ZONE TYPE LABEL ADDR ZONE TYPE LABEL 1 43 85 2 44 86 3 45 87 4 46 88 5 47 89 6 48 90 7 49 91 8 50 92 9 51 93 10 52 94 11 53 95 12 54 96 13 55 97 14 56 98 15 57 99 16 58 100 17 59 101 18...

Page 16: ...work or panel conditions This LOG BOOK must be available for inspection at all times You can photocopy this log book to provide extra pages for when this book is full BS5839 part 1 recommends that fir...

Page 17: ...PANEL r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 16 Issue 3 09 Author NRPJ Date 25 5 2017 MAINTENANCE WORK DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITIONAL...

Page 18: ...r7255 LOOP r7152 Approved Document No GLT MAN 108 PAGE 17 Issue 3 09 Author NRPJ Date 25 5 2017 MAINTENANCE WORK CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION REASON FOR WORK WORK CARRIED OUT ADDITI...

Page 19: ...T MAN 108 PAGE 18 Issue 3 09 Author NRPJ Date 25 5 2017 UNWANTED FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINTENAN...

Page 20: ...108 PAGE 19 Issue 3 09 Author NRPJ Date 25 5 2017 UNWANTED FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION CAUSE IF KNOWN OR ACTIVITIES IN ALARM AREA MAINTENANCE VISIT NEEDED YES NO MAINT...

Page 21: ...oved Document No GLT MAN 108 PAGE 20 Issue 3 09 Author NRPJ Date 25 5 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING CAUSE...

Page 22: ...Document No GLT MAN 108 PAGE 21 Issue 3 09 Author NRPJ Date 25 5 2017 ALL EVENTS OTHER THAN MAINTENANCE WORK OR FALSE ALARMS CONTINUED DATE TIME LOOP ADDRESS ZONE LOCATION DETAILS OF EVENT INCLUDING C...

Page 23: ...27V All call points detectors can signal an alarm condition and indicate the correct zone and text message on the fire alarm panel The Sound pressure level throughout the building should be checked fo...

Page 24: ...t the said design for which I we have been responsible complies to the best of my our knowledge and belief with the recommendations of section 2 of BS 5839 1 for the system category described below ex...

Page 25: ...s applicable for min Appropriate guidance has been provided to the user to enable limitation of false alarms Other measures as follows INSTALLATION COMMISSIONING RECOMMENDATIONS It is strongly recomme...

Page 26: ...ith the specifications described below and with the recommendations of BS5839 1 except for the variations if any stated in this certificate Name Block Letters Position Signature Date For on behalf of...

Page 27: ...endations of BS 5839 1 All equipment operates correctly Installation work is as far as can be reasonably ascertained of an acceptable standard The entire system has been inspected and tested in accord...

Page 28: ...y this certificate All installation work appears to be satisfactory The system is capable of giving a fire alarm signal The facility for remote transmission of alarms to an alarm receiving centre oper...

Page 29: ...7 2012 Updated images Fixed Formatting 3 06 26 7 2012 Fixes Table Errors Corrected references to Quatro Panel to Simplicity Panel Moved Modification History back to first page Realigned Page Breaks U...

Reviews: