SIMPLICITY PLUS USER MANUAL, MAINTENANCE GUIDE & LOG BOOK
Software Versions: PANEL r7255 & LOOP r7152
Approved Document No: GLT.MAN-108
PAGE 9
Issue 3.09 Author: NRPJ Date: 25/5/2017
will show Positive or Negative to help the engineer locate the problem.
*** FAULT ***
1 of 1
Earth Fault Pos
Sounder Fault
If there is a fault on the loop sounders, the line sounder fault LED will light along with the zone that contains that sounder. Because
the sounder is addressable, any fault will be indicated as a device fault.
*** Device Fault ***
1 of 1
Corridor Sounder 1
Zone:01 Ad:012
6.2 WHAT TO DO IF A FAULT CONDITION OCCURS
If a fault occurs, the responsible person should:
Turn keyswitch to Controls enabled and press silence flt tone button to silence the fault buzzer.
Write down the fault (s) in the Log Book at the back of this Manual. Take appropriate action to correct the fault (Usually by
contacting the service engineer)
On the Simplicity panel, the fault indications (except system fault) are non latching. That is, when the fault has been cleared, the
fault indication will turn off. When all faults have been cleared, the panel will return to its quiescent (normal) condition.
When a fault has been rectified the indicator light for that Fault is automatically turned off. If all Faults are cleared, the General Fault
light will go out and the Panel’s Internal Sounder will be silent (if not already muted).