Function
code
Name
Description
Setting
range
Factory
default
F5.07
Programmable relay
R output
0
:
NO output
1
:
VFD
ready to run
2
:
Running indication signal
3
:
VFD zero-speed running
4
:
External fault stop
5
:
VFD fault
6
:
Frequency/speed arrival signal (FAR)
7
:
Frequency/speed level detection signal (FDT)
8
:
Upper limit arrival of output frequency
9
:
Lower limit arrival of output frequency
10
:
VFD overload
11
:
Timer time is up(When the timing time
reaches the timing setting time of Fb.13, the relay
outputs)
12
:
Counter reaches the set value(When the
count value reaches the counter detection value
of Fb.12, the relay will output)
13
:
Counter reset signal (reserved)
14
:
Reserved
0-14
5
F5.08
R output delay time
F5.09
R turn off delay time
F5.10
Frequency arrival
detectionrange (FAR)
When the output frequency is within the positive
and negative detection width of the set frequency,
the terminal outputs a valid signal (low level)
0.00-15.00Hz
5.OOHz
F5.11
FDT level setting
0.00-Upper
limited
frequency
10.00Hz
F5.12
FDT lag
0.00
~
30.00Hz
1.00Hz
F5.13
UF/DOWN terminal modification
rate
Set the frequency modification rate when the
UP/DOWN terminal sets the frequency. That is,
the UP/DOWN terminal is short-circuited with
COM for one second, the magnitude of the
frequency change.
0.10-
200.00Hz/s
1.00Hz
F5.14
Reserved
F5.15
Effective logic setting
of input terminal (X1
-
X5)
Bit0 to Bit4 correspond to X1 to X5 respectively
0 is positive logic, i.e. terminal Xi is enabled when
it connects with common terminal and disabled if
disconnected.
1 is negative logic, i.e. terminal Xi is disabled
when it connects with common terminal and
enabled when disconnected.
0-31
0
F5.16
X1 filter coefficient
0-9999
5
F5.17
X2 filter coefficient
0-9999
5
F5.18
X3 filter coefficient
0-9999
5
F5.19
X4 filter coefficient
0-9999
5
F5.20
X5 filter coefficient
0-9999
5
0.0s
Used to set the sensitivity of the input terminals.
If
the digital input terminals are susceptible to
interference and cause malfunction, this
parameter can be increased to increase the
resistance to
interference. However, setting it too high will
result in a reduction in the sensitivity of the input
terminals.
1: represents the unit of 2MS scan time
The delay from the change of the state of relay R
to the change of the output
0-999.9s
1
3