1.4 - REQUIRED UPSTREAM PROTECTIONS
•
Class-I/B Lightning Protection must be connected to the upstream distribution panel. Min.
cable length between the charger and the protection device recommended to be 10m. *The
charger contains Class II/C Type Surge Protector Device (SPD) – Phoenix, VAL-MS230/3+1 FM
•
MCCB (Thermic Magnetic Adjustable) must be connected to the upstream distribution box.
Model
CC
S
CHADEMO
AC Sock
et
Po
w
er Out
Input Max AC curr
ent
Rec
ommended Cr
os
s
Section f
or
L1-L2-L3 (mm2)
Rec
ommended Cr
os
s
Section f
or Neutr
al
Rec
ommended Cr
os
s
Section
for PE (mm2)
Requir
ed Cir
cuit
Br
eak
er
EVC06- DC-
60CHS
30
30
22
60kW+22kW
151A
70
16
70
200 A
TMF
EVC06-
DC60CCS
30
30
22
60kW+22kW
151A
70
16
70
200 A
TMF
EVC06- DC-
60CS
60
-
22
60kW+22kW
151A
70
16
70
200 A
TMF
EVC06-
DC60C
60
-
-
60kW
151A
70
16
70
200 A
TMF