Installation –
Mounting Height & Clearance
6
www.zephyronline.com
DUCTING
A minimum of 6” round or 3-1/4” x 10” rectangular
duct must be used to maintain maximum air ow
ef ciency for single blower and 10” round duct for
dual blower.
Always use rigid type metal ducts only. Flexible
ducts could restrict air ow by up to 50%.
Also use calculation (on page 5) to compute total
available duct run when using elbows, transitions
and caps.
ALWAYS, when possible, reduce the number or
transitions and turns. If long duct run is required,
increase duct size from 6” to 7” or 8”.
If turns or transitions are required; install as far
away from hood duct output and as far apart,
between the two as possible.
Minimum mount height between range top to hood
bottom should be no less than 26”.
Maximum mount height should be no higher than
36”.
It is important to install the hood at the proper
mounting height. Hoods mounted too low could
result in heat damage and re hazard; while hoods
mounted too high will be hard to reach and will
lose its performance and ef ciency.
If available, also refer range manufacturer’s height
clearance requirements and recommended hood
mounting height above range.
Vertical Ducting:
6” round minimum (singe blower)
10” round minimum (dual blower)
Horizontal Ducting:
3-1/4”x10” minimum (single blower)
No horizontal option available for dual blower
11"
36"
96"
Min 26” - Max 36"
Summary of Contents for AK7000AS
Page 2: ...www zephyronline com...